Using calibration management, Unable to run the procalv5 software – Rockwell Automation FactoryTalk AssetCentre Installation Guide 5.0 User Manual

Page 86

Advertising
background image

7

T

ROUBLESHOOTING

F

ACTORY

T

ALK

A

SSET

C

ENTRE

INSTALLATION

80

• •

Using Calibration Management

“No ProCalV5 Server connection information exists on the
FactoryTalk AssetCentre server” appears when attempting to
use Calibration Management features

This error message is displayed when you attempt to use the Calibration Management
capability, but have not installed the FactoryTalk AssetCentre Calibration Management
server. See “Installing the ProCalV5 server software after the FactoryTalk AssetCentre
server” on page 36.

This error message is also displayed if you have installed the FactoryTalk AssetCentre
Calibration Management server, but have not run the ProCalV5 Data Source Edit Wizard.
See “Running the ProCalV5 Data Source Edit Wizard” on page 36.

“Error executing ProCalV5 commands, check ProCalV5
installation” appears when attempting to use Calibration
Management features

This error message is displayed when you attempt to use the Calibration Management
capability, but have not installed the FactoryTalk AssetCentre Calibration Management
client. See “FactoryTalk AssetCentre Calibration Management client software installer”
on page 47.

“Error initializing FactoryTalk AssetCentre. Could not load file
or assembly… CalibrationPlugin.dll” appears when attempting
to start the client

This message is displayed when you start the FactoryTalk AssetCentre client if the
FactoryTalk AssetCentre Calibration Management client was not installed in the same
directory as the FactoryTalk AssetCentre client. To fix this problem, you must uninstall
and then reinstall the FactoryTalk AssetCentre client, making sure to install the
FactoryTalk AssetCentre Calibration Management client in the same directory as the
FactoryTalk AssetCentre client. See “Installing FactoryTalk AssetCentre clients” on
page 38.

Unable to run the ProCalV5 software

You must be logged on to the client computer as an administrator or as a user with
administrative privileges to run the ProCalV5 software from within FactoryTalk
AssetCentre.

FTAC-IN005A-EN-E.book Page 80 Monday, March 4, 2013 4:03 PM