Connecting to the field network, Preparing the communication cable, Connecting to the field network -4 – KEYENCE LK-CC100/DN100 User Manual

Page 40: Preparing the communication cable 3-4

Advertising
background image

3-4

3

3 Connecting to DeviceNet

Connecting to the Field Network

To connect to the master device or network controller on the field network using a

multidrop connection, or to connect other slave devices, connect a communication cable

that supports each field network to the field network connector.

Preparing the communication cable

Use a 5-wire communication cable dedicated for DeviceNet.

1

Remove the sheath (outer insulation) from the cable.

Remove about 70 mm from the end of the cable.

Leave 6 mm or less of the braided shield exposed.

2

Cover with a shrink tube.

Cover the exposed conductors and sheath with a shrink tube cut to about 40 mm.

3

Strip the insulation from each conductor.

Strip about 8 mm from the end of each conductor.

6 mm max.

Approx. 70 mm

Braided shield wires

Sheath

Approx. 40 mm

Shrink tube

Sheath

Approx. 8 mm

Insulated conductor