Timing diagrams, Timing diagrams -20 – KEYENCE LK-CC100/DN100 User Manual

Page 56

Advertising
background image

3-20

3

3 Connecting to DeviceNet

Timing Diagrams

This is the timing diagram for a control input.

• OUT: Master

 slave

• IN: Slave

 master

• Internal: Internal processing at the slave

• Control inputs that do not have the ***_STATE flag follow the same timing except that the ***_STATE

flag is omitted.

• The X axis shows the correct timing but not the exact time.

Normal timing (status change from OFF

ON)

Abnormal timing (error, status stays ON)

Reference

1 ***_REQ

OUT

3 ***_ACQ

Verify ***_ACQ is OFF, then turn ***_REQ ON.

IN

4 ***_ERR

IN

5 ***_STATE IN

2 Internal
processing

1 ***_REQ

OUT

3 ***_ACQ

IN

4 ***_ERR

IN

5 ***_STATE IN

2 Internal
processing

Issue the next ***_REQ after
verifying ***_ACQ has gone LO.

***_ACQ turns ON after
***_ERR changes state.

***_STATE does not change if ***_ERR goes to HI
because no processing is performed.

***_ERR changes to the OFF state at the
same time ***_ACQ turns OFF.

Verify ***_ACQ is OFF, then turn ***_REQ ON.