Wiring to the devicenet controller (lk-dn100), Wiring to the devicenet controller, Lk-dn100) -6 – KEYENCE LK-CC100/DN100 User Manual

Page 42: Typical connection, Connecting terminators

Advertising
background image

3-6

3

3 Connecting to DeviceNet

Wiring to the DeviceNet controller (LK-DN100)

The LK-DN100 field network connector (terminal block) is to be wired as explained below.

Connect the cable by matching the color of the wires to the colors on the sticker affixed to the
DeviceNet connector.

Typical connection

Refer to the manual for the DeviceNet master unit for wiring details.

Connecting terminators

A terminator must be connected to both ends of the

trunk line. The terminators must be connected to

reduce signal reflection and stabilize communication.

Terminator resistance: metal-film resistor 121 ohms,

1%, 1/4W

The terminators must be connected, otherwise, DeviceNet will
not communicate properly.

Terminal
name

Wire
color

Function

V+

Red

Communication power supply (24 VDC input)

CAN_H

White

Communication signal High

SHIELD

Exposed Shield

CAN_L

Blue

Communication signal Low

V-

Black

Communication power supply (0 VDC input)

V+

CAN H

SHIELD

CAN L

V-

NOTE

Terminator

Terminator

LK-DN100

Other unit

Other unit

Master node

Other unit

LK-DN100

CAN H

CAN L

Terminator

V+

CAN H

SHIELD

CAN L

V-