3 Connecting to DeviceNet

Output control buffer

The output control buffer refers to control signals sent from the DeviceNet master node to

the LK-DN100.

LK-
DN100

Signal
direction

DeviceNet master node

Offset

Signal name

Explanation

Read
control
buffer

Bit (0)

CHG_PRG_REQ

• Requests to change to the program

number stored in SET_PRG_NUM at the
rising edge from OFF (0)

 ON (1).

• Ends the request at the falling edge from

ON (1)

OFF (0).

Bit (1)

System reserved

Bit (2)

SYNC_TIM_ON_REQ

• Requests synchronized timing ON at the

rising edge from OFF (0)

 ON (1).

• Ends the request at the falling edge from

ON (1)

 OFF (0).

Bit (3)

System reserved

Bit (4)

SYNC_TIM_OFF_REQ

• Requests synchronized timing OFF at

the rising edge from OFF (0)

 ON (1).

• Ends the request at the falling edge from

ON (1)

 OFF (0).

Bit (5)

System reserved

Bit (6)

SYNC_ZERO_ON_REQ

• Requests synchronized zero ON at the

rising edge from OFF (0)

 ON (1).

• Ends the request at the falling edge from

ON (1)

 OFF (0).

Bit (7)

System reserved

Bit (8)

SYNC_ZERO_OFF_REQ

• Requests synchronized zero OFF at the

rising edge from OFF (0)

 ON (1).

• Ends the request at the falling edge from

ON (1)

 OFF (0).

Bit (9)

System reserved

Bit (10)

SYNC_RESET_REQ

• Requests synchronized reset at the

rising edge from OFF (0)

 ON (1).

• Ends the request at the falling edge from

ON (1)

 OFF (0).

Bit (11)

System reserved

Bit (12)

System reserved

Bit (13)

System reserved

Bit (14)

System reserved

Bit (15)

System reserved

Bit (16*m+0)

System reserved

Bit (16*m+1)

System reserved

Bit (16*m+2)

System reserved