Digital i/o functions, Toshiba – Toshiba LF600F User Manual

Page 115

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOSHIBA

6,F,8,A0,8,6,9,

10. Digital I/O Functions

The LF60*F series electromagnetic flowmeter is equipped with two-contact-point terminals (digital
output terminals: one of them is optional), enabling you to use various functions including pulse
output and alarm output.

Digital I/O functions are described below.

Functions

Necessary DO/DI

Description

Totalization

DO: 1 point

DI: None to

1 point

■ The converter totalizes volumetric flow rate.

■ The totalized volumetric flow can be output (pulse output)

for each unit flow.

■ The totalizer and pulse signal (DOl only) can be controlled

(starts, stops and resets) with an external signal (DI).

Multiple Ranges

DO: 1 to

2 points

DI: None to

1 point

Multiple measuring ranges can be switched according to

the process flow rates either automatically or by an external

signal (DI).

Forward and

Reverse flow

measurements

DO: 1 point

■ Forward and reverse flows can be measured. The forward

and reverse flow measurements can be used together with

multiple range switching function.

High and Low

Limit Alarms

DO: 1 to

2 points

■ Outputs an alarm signal (DOl or D02) when the process

signal exceeds or stays below the limit values.

Totalizer Preset

Point

DO: 1 point

■ When the totalized flow exceeds its preset count value, the

converter outputs a contact output signal (DOl or D02).

Remote Zero
Adjustment

DI: 1 point

■ Zero adjustment (on-stream at zero flow rate) can be started

by an external signal (DI).

Fixed-value

Output

DI: 1 point

■ Fixed current output and fixed pulse output can be used to

check a process loop circuit. An external signal (DI) can also

be used to control this fixed-value output.

Converter

Failure Alarm

DO: 1 point

■ The converter outputs an alarm signal (DOl or D02) if

an error such as memory error or excitation circuit error

occurs.

Multiple range
High/Low alarm

(option)

DO: 2 points
DI: 1 point

■ Flow rate high/low alarm and high-high/low-low alarm

are switched interlocking with the switching of high/low

range by external input signal, and output HH/LL alarm.

-

114

-

Advertising
This manual is related to the following products: