5.3 Notes on Wiring

5.3.1 Notes on Instrumentation-Converter Wiring

• To avoid 2-point grounding, ground the shield of output cable basically at the receiving side.
• Use a grounding wire of IV wire 5.5mm^ or more. The size of the external grounding terminal screws is

M4. Do not share a grounding wire with other instruments where grounding current may flow. (An
independent grounding is preferable.)

• Power cable

When a 3-core cable is used: Ground with the FG terminal.
When a 2-core cable is used: Use an external grounding terminal and make the cable as short as possible.

Note that, for a replacement from the Toshiba electromagnetic flowmeter converter LF220 type, the

cable grounding position differs.

m

LF602F

5.3.2 Notes on Wiring of the LF602F Type

• The detector is shipped with a flow rate signal cable and excitation cable. Be sure to use those cables

coming with the detector.

Note: When the cable length exceeds 30m, cables may not be supplied. Check whether the
cable is supplied with the specs.

• The allowable cable length between the detector and converter varies depending on the conductivity of

the operating fluid. Refer to the instruction manual of the combined detector.

• When connecting with the detector, wire the cables in the order of the excitation cable and flow rate

signal cable.

• Because the input cables transmit very delicate signals, pass the excitation cable and input signal cable

separately through a thick steel conduit tube , keep them away from the large current wiring as
far as possible, and do not install them in parallel.

• When replacing the flow rate signal cable and excitation cable, also refer to the instruction manual of the

relevant detector. Order the detector terminal box cover packing from Toshiba or a Toshiba distributor.

-