High and low limit alarms, high-high and low-low limit alarms, empty alarm

One of the following messages appears if the flow rate reading goes out of the set range or an
empty alarm is generated.

If the high or low limit alarm enable/disable status is set to OFF, its alarm function (high or low) is

disabled. See 0, “Check/Change of Parameters.”

LCD display

Description

Corrective action

H

1

G

H

A

L

A

R

M

If high limit alarm is set, the

flow rate reading exceeds the
setting value.

Adjust so that the reading

stays below the high limit.

L

0

W

A

L

A

R

M

If low limit alarm is set, the flow
rate reading is below the

setting value.

Adjust so that the reading
stays above the low limit.

H

1

G

H

H

1

G

H

If high-high limit alarm is set,

the flow rate reading exceeds
the setting value.

Adjust so that the reading
stays below the setting

value.

A

L

A

R

M

L

0

W

L

0

W

If low-low limit alarm is set, the

flow rate reading is below the

setting value.

Adjust so that the reading
stays above the setting
value.

A

L

A

R

M

E

M

P

T

Y

A

L

A

R

M

Indicates that the detector pipe

is empty.

Fill the pipe with fluid.

The measured value is over

125%.

The measurement value
setting range is too narrow

or a larger volume of fluid

is flowing. Check whether

the setting is correct or if
there is any problem in

processing.

0

V

E

R

1

2

5

%

The measure value is below
-125%.

The measurement value
setting range is too narrow
or a larger volume of fluid
is flowing. Check whether

the setting is correct or if
there is any problem in

processing.

U

N

D

E

R

-

1

2