8.2.15 Low Cutoff

The low cutoff is the value set just above 0% flow rate. Flow rates below this level are treated as
0%, i.e. the current output is forcibly changed and fixed to 0%.
The low cutoff can be set from 0 to 10% of the span and in increments of 0.1%.
Proceed as follows to check or change the low cutoff value.

Shown below is an example of changing the low cut value from 1.0% to 3.0%.

Key operation

Display example

Description

D:

MEAS MODE

DAMPING

-^LOWCUT

ALM mA SET

DSP LOW CUT

LOW LIMIT

iSELl [ENT

Select "LOW CUT" in the configuration item

selection screen.

STEP1

[ENT]

D2:

LOW CUT

01.0

%

[EXE fENTl

The currently set low cut value (1.0% in this

example) is displayed.

Then press the [ENT] key.

* Pressing the [EXT] key returns you to the menu screen.

STEP2

[ENT]

D2:

LOW CUT

01.0

%

[U PI [SELl fSETl

The switch name display at the bottom changes (three

keys [UP], [SEL] and [SET])

At the same time, the cursor appears.

(The digit on which the cursor is positioned is

reverse-displayed.)

STEP3

[SEL]0[UP]

D2:

LOW CUT

00.0

%

[U P] [SEL] [SET]

Move the cursor to the desired digit using the [SEL] key

and change the numeric value using [UP] key.

Repeat this operation to change the setting value to 3.0%.

When the value has changed to the desired value, press

the [SET] key to set the low cut value

temporarily.

STEP4

[SET]

D2:

LOW CUT

03.0

^

%

OK? ^

IN 01 fSETl

When you press the [SET] key, a message confirming you

whether the setting is OK is displayed.

If OK, press the [SET] key. If you want to redo the setting,

press the [NO] key.

STEP5-1

[NO]

D2;

LOW CUT

01.0

%

[U PI [SELl [SET!

Pressing the [NO] key when you are asked "OK?" causes

the low cut value to return to the previous value and

enables you to redo the setting.

STEP5-2(=END)

[SET]

D2:

LOW CUT

03.0

%

____

ШП

_________Щ]______

Pressing the [SET] key when you are asked "OK?" causes

the setting to be determined.

Then press the [EXT] key. You return to the menu screen.

Pressing the [ENT] key enables you to restart low cut

value change operation from a state of 3.0%.

Note If you set a value exceeding 10.0%, *HIGH OVER SPEC.* is displayed and the setting

returns to the one before change. Set a value once again.

-