DECS-100 General Information

9287500991 Rev M

Style Number Example

For example, a DECS-100 with a style number of A15 would have the following characteristics and
operating features.

A ------- No var or power factor control
1 -------- Voltage matching
5 -------- 5 ampere current sensing

SPECIFICATIONS

DECS-100 specifications and qualifications are listed in the following paragraphs.

Operating Power

Refer to Section 4, Installation for special requirements concerning the application of operating power
during DECS-100 programming and the application of station power.

Voltage:

88 to 250 Vac, single-phase or three-phase (L-L)

Frequency:

50 to 400 Hz

Power Dissipation:

40 W (maximum continuous)

Burden:

650 VA

Voltage Buildup:

≥6 Vac

Terminals:

3, 4, 5

Generator Voltage Sensing

Type:

1-Phase/3-Phase, 4 ranges

Burden:

<1 VA per phase

Terminals:

E1, E2, E3

50 Hertz Sensing

Range 1:

100 Vac (85 to 132 Vac)

Range 2:

200 Vac (190 to 220 Vac)

Range 3:

400 Vac (380 to 440 Vac)

Range 4:

N/A

60 Hertz Sensing

Range 1:

120 Vac (85 to 132 Vac)

Range 2:

240 Vac (170 to 264 Vac)

Range 3:

480 Vac (340 to 528 Vac)

Range 4:

600 Vac (540 to 660 Vac)

Generator Current Sensing

Type:

1-phase (B-phase), 50/60 Hz

Style XX1:

1 Aac maximum continuous

Style XX5:

5 Aac maximum continuous

Burden:

<0.1 VA

Terminals:

CT1, CT2

Bus Voltage Sensing (Optional)

Type:

1-phase, 4 ranges

Burden:

<1 VA per phase

Terminals:

B1, B3

50 Hertz Sensing

Range 1:

100 Vac (85 to 132 Vac)

Range 2:

200 Vac (190 to 220 Vac)

Range 3:

400 Vac (380 to 440 Vac)

Range 4:

N/A

60 Hertz Sensing

Range 1:

120 Vac (85 to 132 Vac)

Range 2:

240 Vac (170 to 264 Vac)

Range 3:

480 Vac (340 to 528 Vac)

Range 4:

600 Vac (540 to 660 Vac)