Parallel Generator Compensation

A customer-supplied enable/disable contact for this function connects to the terminals labeled 52L and
52M.

Only dry, ungrounded switching contacts should be applied to the Parallel Generator Compensation
contact input.

Parallel Control and Var/PF Control Inputs

User-supplied contacts at terminals 52L and 52M determine whether AVR or Droop mode is active.
Terminals 52L and 52M typically connect to a 52b auxiliary contact of the generator breaker. User-
supplied contacts at terminals 52J and 52K control whether var or power factor correction is active or
disabled. Terminals 52J and 52K typically connect to the auxiliary contacts of the utility tie breaker. Table
4-3 lists the operating modes achieved for the different 52L/M and 52J/K contact states. A closed state
indicates a continuous contact closure and an open state indicates a continuous open-circuit.

Table 4-3. 52L/M and 52J/K Control Modes

DECS-100 Operating Mode

52L/M

52J/K

Generator Operating Mode

AVR mode active, no droop, optional
var/PF mode disabled

Closed

Closed

Single unit/stand-alone

Droop mode active, optional var/PF
mode disabled

Open

Closed

Paralleled to the utility grid (droop) or
two or more generators islanded
(droop or CCC)

Var/PF mode active

Open

Open

Paralleled to utility grid

Voltage Matching (Optional)

A customer-supplied enable/disable contact for this function connects to the terminals labeled VM and
VMC. Only dry, ungrounded switching contacts should be applied to the Voltage Matching contact input.

Voltage matching is also enabled/disabled by the state of the 52J/K and/or 52L/M contact inputs. In
BESTCOMS™, voltage matching can be configured to be disabled when the 52J/K or 52L/M contact input
is open or just the 52J/K contact input is open.

Power Supply Inputs

Power input terminals are labeled 3, 4, and 5. Single-phase or three-phase power may be applied. Single-
phase power may be applied to any two of the three terminals.

The DECS-100 can be powered directly from a variety of sources as long as the DECS-100 input power
specifications are followed (see Section 1, General Information, Specifications).

Examples of DECS-100 operating power sources are:
• Generator (shunt fed)
• Permanent magnet generator (PMG)
• Auxiliary winding

When powering the DECS-100 from a low-impedance power source, special provisions must be made to
avoid damage to the DECS-100. Examples of a low-impedance power source include a station service
source or power outlet. An Inrush Current Reduction Module, ICRM-7, must be connected between the
power source and DECS-100 input power terminals (see Figure 4-10). The ICRM-7 prevents DECS-100
damage by minimizing the level of inrush current. The ICRM-7 can also be used when programming the
DECS-100. However, the Preliminary Setup paragraphs illustrate an alternate method for temporarily
powering the DECS-100 for programming.

More details about the ICRM-7 are available in Basler Electric publication 9387900990.

Chassis Ground

The chassis ground terminal is labeled GND.

Power (Field) Output

The field output terminals for connection to the generator exciter field are labeled F+ and F–.