Figure 5-9. Control Gain Screen

Table 5-1. DECS-100 Stability Range Settings

Generator

Size

Time Constants

Stability

Range

Generator (T’do)

Exciter (Texc)

SMALL

1.0

0.17

1

1.5

0.25

2

2.0

0.33

3

2.5

0.42

4

3.0

0.50

5

3.5

0.58

6

4.0

0.67

7

4.5

0.75

8

5.0

0.83

9

5.5

0.92

10

6.0

1.00

11

6.5

1.08

12

7.0

1.17

13

7.5

1.25

14

8.0

1.33

15

8.5

1.42

16

9.0

1.50

17

9.5

1.58

18

10.0

1.67

19

LARGE

10.5

1.75

20

AVR/FCR - Integral Gain KI. This setting selects the integral constant (KI) stability parameter. The DECS-
100 supplies a value that is equivalent to KI multiplied by the integral of the error between the voltage
setpoint and the actual generator output voltage. KI values of 0.01 to 1,000 may be entered in increments
of 0.01.

Increasing the value of KI decreases the time required to reach steady state.