DECS-100 General Information

1-5

Overexcitation Limiter

Pickup

Range:

0 to 15 Adc

Increment:

0.001 Adc

Alarm Time Delay

Range:

0 to 10 s

Increment:

1 s

Underexcitation Limiter

Pickup

Range:

0 to 100% of rated vars

Increment:

1%

Alarm Time Delay

Range:

0 to 10 s

Increment:

1 s

Soft Start Function (AVR Mode Only)

Time Adjust Range:

1 to 7,200 s

Increment:

1 s

Voltage Matching

Accuracy:

Generator rms voltage is matched with the bus rms voltage to within
±0.5% of the generator voltage.

Time Adjustment

Range:

1 to 300 s

Increment:

0.01 s

Metering (BESTCOMS™)

Generator Voltage

Range:

10 V to 79 kV

Accuracy:

±0.5% (at 25

°C)

Generator Current

Range:

0.04 to 3,000 Aac for 1 A CT (Not to exceed nominal CT rating)

0.2 to 15,000 Aac for5 A CT (Not to exceed nominal CT rating)

Accuracy:

±0.5% (at 25

°C)

Frequency

Range:

40 to 65 Hz

Accuracy:

±0.2 Hz (at 25

°C)

Field Voltage

Range:

0 to 200 Vdc

Accuracy:

±5.0% (at 25

°C)

Field Current

Range:

0 to 20 A

Accuracy:

±0.5% (at 25

°C)

Bus Voltage

Range:

10 V to 79 kV

Accuracy:

±0.5% (at 25

°C)

Auxiliary DC Input

Range:

–3 V to +3 V

Accuracy:

±0.5% (at 25

°C)