Fcr (manual) operating mode, Var operating mode (optional), Pf operating mode (optional) – Basler Electric DECS-100 User Manual

Page 16: Parallel compensation, Field overvoltage protection, Generator overvoltage protection, Fcr (manual) operating mode -4, Var operating mode (optional) -4, Pf operating mode (optional) -4, Parallel compensation -4

Advertising
background image

1-4

DECS-100 General Information

9287500991 Rev M

Figure 1-2. Typical V/Hz Curves

FCR (Manual) Operating Mode

Adjustment Range:

0 to 7 Adc

Increment:

0.01 Adc

Var Operating Mode (Optional)

Adjustment Range:

–100 to 100%

Increment:

0.1%

PF Operating Mode (Optional)

Adjustment Range:

0.6 lag to 0.6 lead

Increment:

0.001

Parallel Compensation

Modes:

Reactive Droop and Reactive Differential (cross-current)

Droop Adjust Range:

0 to 10%

Increment:

1%

∗ Burden can exceed 1 VA if external resistors are added to the CT circuit.

Field Overvoltage Protection

Pickup Range:

0 to 250 Vdc

Time Delay:

10 s (fixed)

Generator Overvoltage Protection

Pickup

Range:

100 to 120% of system voltage setting

Increment:

1.0%

Alarm Time Delay

Range:

0 to 10 s

Increment:

1 s