DECS-100 General Information

1-3

Accessory Input

Voltage Range:

–3 Vdc to +3 Vdc

Setpoint Range:

–30% to +30% shift

Burden:

1 k

Terminals:

A, B

Communication Port

Interface:

Full duplex RS-232

Connection:

Rear panel DB-9 connector

Baud:

4800

Data Bits:

8

Parity:

None

Stop Bit:

1

Contact Input Circuits

Type:

Dry contacts

Interrogation Voltage:

13 Vdc (supplied by DECS-100)

Terminal Assignments for Standard Functions

Raise:

6U, 7

Lower:

6D, 7

Var/PF Enable:

52J, 52K

Parallel Control:

52L, 52M

Voltage Matching:

VM, VMC

Common Alarm Output

Type:

Form A

Rated Load:

7 Aac/Adc continuous

Make:

30 Aac/Adc, carry for 0.2 sec

Break:

7 Aac/0.1 Adc

Operating Voltage:

240 Vac/250 Vdc maximum

Terminals:

AL1, AL2

Field Output

Continuous Rating:

63 Vdc, 7 Adc

Field Resistance:

9

Ω minimum

Terminals:

F+, F–

10 Second Forcing Rating

200 Vac Power Input:

135 Vdc, 15 Adc

110 Vac Power Input:

90 Vdc, 10 Adc (9

Ω field)

75 Vdc, 15 Adc (5

Ω field)

AVR Operating Mode

Adjustment Range:

See Generator Voltage Sensing

Voltage Regulation:

±0.25% over load range at rated power factor and constant generator
frequency.

±0.5% with 3-phase sensing and shunt power at 40% THD of the voltage
waveform (due to a six SCR load).

Temperature Drift:

±0.5% for a 40

°C change

V/Hz Characteristic:

Slope from 0 to 3PU is adjustable in 0.01PU increments. Transition
(Corner) frequency is adjustable from 40 to 65 Hz. See Figure 1-2 for the
V/Hz curves.

Response Time:

Within 1 cycle