Installation for emc compliance, Protection, Mounting – Basler Electric DECS-100 User Manual

Page 48: Wiring, Ferrite beads, Installation for emc compliance -14, Protection -14, Mounting -14, Wiring -14, Ferrite beads -14

Advertising
background image

4-14

DECS-100 Installation

9287500991 Rev M

Clamp

Ferrite

Grade

Frequency Range

Terminals

2

31

1 MHz – 300 MHz

VM, VMC – Voltage Matching

52L, 52M – Parallel Gen. Compensation

3

31

1 MHz – 300 MHz

E1, E2, E3 – Sensing Voltage

4

31

1 MHz – 300 MHz

3, 4, 5 – AC Power Input

5

31

1 MHz – 300 MHz

CT1, CT2 – Current Sensing

INSTALLATION FOR EMC COMPLIANCE

The following paragraphs describe the mounting and wiring requirements for an EMC (Electromagnetic
Compatibility) compliant installation.

Protection

Internal DECS-100 protection functions must not be used as the primary form of generator protection.

Mounting

The DECS-100 must be mounted inside a grounded, metal, EMC type enclosure (conduit box) with a
grounded, metal access panel which covers the opening for the DECS-100 front panel display.

Wiring

Wiring connected to the terminals listed below must be shielded. Each shield should be terminated to
ground on the outside of the metal enclosure (conduit box).
• Sensing voltage terminals E1, E2, and E3
• Alarm output terminals AL1 and AL2
• External voltage adjust terminals 6D, 7, and 6U
• Var/Power Factor control contact input terminals 52J and 52K
• Parallel generator compensation terminals 52L and 52M
• Field terminals F+ and F-
• AC power input terminals 3, 4, and 5
• Voltage matching contact input terminals VM and VMC

Ferrite Beads

Install one ferrite clamp, with the properties listed in Table 4–6, on the wires connected to the terminals
listed in the same row with two turns at the enclosure’s exit or inside the enclosure between 1 and 3
inches (25 and 76 mm) from the connector.

Table 4-6. Ferrite Clamp Specifications and Corresponding Wire Terminals

Clamp

Ferrite

Grade

Frequency Range

Terminals

1

31

1 MHz – 300 MHz

AL1, AL2 – Alarm outputs

6D, 7, 6U – External Voltage Adjust

52J, 52K – Var/Power Factor Control

2

31

1 MHz – 300 MHz

VM, VMC – Voltage Matching

52L, 52M – Parallel Gen. Compensation

3

31

1 MHz – 300 MHz

E1, E2, E3 – Sensing Voltage

4

31

1 MHz – 300 MHz

3, 4, 5 – AC Power Input