Figure 5-11. analysis screen, fcr tab -10 – Basler Electric DECS-100 User Manual

Page 62

Advertising
background image

5-10

DECS-100 BESTCOMS™ Software

9287500991 Rev M

The sensing values and alarm signal indicators of the FCR tab are also displayed by the other tabs of the
Analysis screen.

Field Current Step Response - FCR Setpoint (A). This read-only field indicates the FCR setpoint. (The
FCR setpoint is set by using the Setpoint tab of the Setting Adjustments screen). The current displayed in
the FCR Setpoint field is selected by clicking the adjacent pushbutton. Clicking this button sends the FCR
Setpoint value to the DECS-100 and changes the color of the pushbutton from gray to red.

Field Current Step Response - Increment of FCR Setpoint (A). These two fields indicate the increase that
occurs to the FCR setpoint when the corresponding Increment button is clicked. The "% increase" field is
used to set and indicate the percentage (0 to 10%) that the FCR setpoint is increased when the
Increment button is clicked. The "FCR Setpoint =" field indicates the value of current that corresponds to
the "% increase" field. Any setpoint value within range or higher than the setpoint value can be typed into
the "FCR Setpoint =" field, which updates the "% increase" field. The FCR setpoint changes to this value
when the adjacent button is clicked. When clicked, the Increment button changes from gray to red to
indicate that the FCR setpoint has increased to the value in the "FCR Setpoint =" field.

Figure 5-11. Analysis Screen, FCR Tab

Field Current Step Response - Decrement of FCR Setpoint (A). These two fields indicate the change that
will occur to the FCR setpoint when the corresponding Decrement button is clicked. The "% decrease"
field is used to set and indicate the percentage that the FCR setpoint is decreased when the Decrement
button is clicked. The "FCR Setpoint =" field indicates the value of current that corresponds to the "%
decrease" field. The FCR setpoint changes to this value when the adjacent button is clicked. When
clicked, the Decrement button changes from gray to red to indicate that the FCR setpoint has decreased
to the value in the "FCR Setpoint =" field.

Field Current Step Response - Meter Value. This field and the dial pointer indicate the value of the
selected FCR setpoint. When the AVR setpoint is changed by clicking the increment, decrement, or
setpoint button, the meter value field and dial pointer indicate the new setpoint value. A new FCR setpoint
can be typed directly into the "Meter Value" field or selected by dragging the dial pointer to the desired
value. The new value is sent to the DECS-100 by clicking the Send button.

Field Current Step Response - Current Setpoint. The active DECS-100 setpoint (adjusted by using any of
the previously mentioned methods) is displayed in this field. To return the FCR setpoint to the nominal
setting, the button adjacent to the "FCR Setpoint (A) (Nominal)" field should be clicked. If the FCR tab is
left to view other tabs or screens without returning the FCR setpoint to nominal, an FCR setpoint dialog
box appears. Clicking the Yes button returns the AVR setpoint to nominal. Clicking No maintains the AVR
setpoint at the current level.