INSTALLATION FOR CE COMPLIANCE

The following paragraphs describe the mounting and wiring requirements for a CE (European
Community) compliant installation.

Mounting

The DECS-100 must be mounted inside a grounded, metal enclosure (conduit box). An access panel
should cover the opening for the front panel display.

Wiring

Wiring connected to the terminals listed below must be shielded. Each shield should be terminated to
ground on the outside of the conduit box.
• Current sensing terminals CT1 and CT2
• Sensing voltage terminals E1, E2, and E3
• Relay output terminals AL1 and AL2
• Var/Power Factor control contact input terminals 52J and 52K
• Parallel generator compensation terminals 52L and 52M
• Raise and lower contact input terminals 6U, 6D, and 7
• AC power input terminals 3, 4, and 5
• Accessory input voltage terminals A and B
• Voltage matching contact input terminals VM and VMC

Ferrite Clamps

Install one ferrite clamp, with the properties listed in Table 4–5, on the wires connected to the terminals
listed in the same row with two turns at the enclosure’s exit or inside the enclosure between 1 and 3
inches (25 and 76 mm) from the connector.

Table 4-5. Ferrite Clamp Specifications and Corresponding Wire Terminals

Clamp

Ferrite

Grade

Frequency Range

Terminals

1

31

1 MHz – 300 MHz

AL1, AL2 – Alarm outputs

6D, 7, 6U – External Voltage Adjust

52J, 52K – Var/Power Factor Control