Typical humidifier installation – Nortec NH-EL Series User Manual

Page 13

Advertising
background image

Installation | 10

Typical Humidifier Installation

Mounting

Pg 13


Steam

Distribution

Pg 15




Controls

Pg 22


Plumbing

Pg 14



Electrical

Pg 21


Figure 4: Typical Humidifier Installation

6 in.

(15 cm)

min.

right

clearance

36 in. (90 cm)

min. front
clearance

24 in.

(60 cm)

min.

3 in. (7.5 cm) Screws

1- 24 VAC
2- Security Loop
3- Common
4- Channel 1
5- Channel 2
6- 5 VDC
7- Ground
8- Blower Pack
9- Blower Pack

On/Off

Controls

Modulation

Controls

E

X
T

E

R
N

A
L

N

H

-

E

L

L

1

L

2

L

3

G

ro

u

n

d

Dedicated

Circuit

Breaker or

Disconnect

NH-EL

EXTERNAL

Cold potable water
150-1200 microsiemens
30-80 psig

Air Gap

½ in NPT

2 in.

(5 cm)

min.

1ft (30 cm)

1 ft (30 cm)

min.

1 – 24 VAC
2 – Security Loop
3 – Common
4 – Channel 1
5 – Channel 2
6 – 10 VDC
7 – Ground
8 – Blower Pack
9 – Blower Pack

0” (0 cm)

right

clearance

6” (15 cm)

recommended

Advertising