Installation | 20

8. Increase diameter either on down slope or install condensate trap.


9. Install condensate traps if steam line > 15 ft (4.5 m).



10. In addition never:



Best

Good

Never

Nortec
Condensate
Trap

Sloping Down

Increase =

Condensate

Blockage

Best

Good

Never

Nortec
Condensate
Trap

Sloping Down

Increase =

Condensate

Blockage

max. 15 ft

(4.5 m)

max. 15 ft

(4.5 m)

Good

Never

> 15 ft

(4.5 m)

max. 15 ft

(4.5 m)

max. 15 ft

(4.5 m)

Good

Never

> 15 ft

(4.5 m)

Never

Install a valve or other obstruction

Never

Never

Reduce Steam Line Size

Install Copper or SST without Insulation

Never

Install a valve or other obstruction

Never

Never

Reduce Steam Line Size

Install Copper or SST without Insulation

Never

Install a valve or other obstruction

Never

Never

Reduce Steam Line Size

Install Copper or SST without Insulation

Never

Install a valve or other obstruction

Never

Never

Reduce Steam Line Size

Install Copper or SST without Insulation

Never

Install a valve or other obstruction

Never

Never

Reduce Steam Line Size

Install Copper or SST without Insulation

After Installation Always:

Purge steam lines to remove any contaminants and installation materials

Ensure all condensate lines / traps flow.