Double unit control wiring (continued) – Nortec NH-EL Series User Manual

Page 34

Advertising
background image

31 | Installation

Double Unit Control Wiring (Continued)

Independent– Two sets of control signals (Double Mode = Independent) wire the controls for
Zone A (cylinder A) to terminal block A and wire the controls for Zone B (cylinder B) to terminal
block B. All control signals must be the same type (Demand/Transducer).


















Figure 27: Independent Mode Control Wiring (Double Unit)

Figure 28: Double Unit Independent Mode Wiring

Zone B (Cylinder B) Controls

Zone A (Cylinder A) Controls .

Connect zone B

controls to

terminal block B

Connect zone A

controls to

terminal block A

B

A

Zone B (Cylinder B) Controls

Zone A (Cylinder A) Controls .

Connect zone B

controls to

terminal block B

Connect zone A

controls to

terminal block A

B

A

1 – 24 VAC
2 – On/Off Loop
3 – Common
4 – Channel 1
5 – Channel 2
6 – 10 VDC
7 – Ground
8 – Blower Pack
9 – Blower Pack

1 – 24 VAC
2 – On/Off Loop
3 – Common
4 – Channel 1
5 – Channel 2
6 – 10 VDC
7 – Ground
8 – Blower Pack
9 – Blower Pack

Advertising