13 | Installation

Mounting with Keyholes

1 The NH-EL Series humidifier is wall mounted using keyholes located on the back of the unit

cabinetry.

2 Use #12 x 3 in. (7.5 cm) screws mounted into 2x4 studs or better. Two screws are needed

for a single unit (NH-EL 010 to 100). Three screws are needed for a double unit (NH-EL 150
to 200).

3 Keyholes are spaced 16 in. (40.6 cm) apart center to center for large units and 11.9 in.

(27.2 cm) apart for small units. Insert screws into the studs until there is 1/4 in. of screw
exposed. Be sure the screws are level to each other.

4 Raise the unit and place the screws through the keyholes. Make sure the unit is level, then

tighten the screws to secure the unit in place.

5 Place “L” Shaped brackets on top of the unit, with holes inline with the studs. Using the

appropriate sized wood screw, fasten the “L” brackets to the studs, securing the unit from
any upward motion. See Figure 6: Mounting with Keyholes.




Figure 6: Mounting with Keyholes

B

A

Install “L” bracket
after hanging
humidifier

#12 x 3 in. (7.5 cm)
Wood Screws

Insert screws so that

1/4 in. (6 mm) exposed,

hang unit, tighten

screws.

Unit Size

Screws

Dim A in (cm)

.

Dim B in. (Cm)

5-30

2

11.9 (30.2)

-

50-100

2

16 (40.6)

-

150-200

3

16 (40.6)

16 (40.6)

SPACE

SPACE

SPACE

SPACE

Note: Use screws longer than 3” (7.5 cm) if drywall or other spacer is present.