Installation | 24

On/Off Control Wiring
















Figure 15: On/Off Controls



Figure 16: Digital On/Off Humidistat

Note: 1

2

3

4

Humidifier will run when circuit between

terminal 1 and 2 on humidifier is closed.
Terminal 1 is 24 VAC Hot, turn unit off to
avoid shorting while wiring.
Digital Humidistat requires 24 VAC power
from terminals 1 and 3 of humidifier.

2520273 - Digital On/Off Duct Humidistat

can also be used for duct high limit. Wire
in series to 3 - Common and 4 - Digital Out
of the humidistat.

Humidifier Terminal Strip

Air Proving

Switch

Duct High

Limit

2548731 - Digital

On/Off Humidistat