Multi mode wiring – Nortec NH-EL Series User Manual
Page 37
Advertising
Installation | 34
Daisy chain pole 1 and 2
of terminal J10 of the
control board.
Do not reverse polarity.
Note:
Slave X
Daisy Chain
up to 16
Humidifiers
Master
Slave 1
Multi Mode Wiring
Connect up to 16 units (equivalent of 1600 lb/hr) using 18-24 AWG multi-strand, twisted
pair, shielded cable.
Connect humidistats/transducers and security loop to master unit only.
Jump the security loops on slave units.
When connecting double units connect only to driver board A.
See NH-EL Humidifier Configuration on page 54 and Multi on page 57 for software
configuration.
Figure 32: Multi Mode Wiring