Nortec NH-EL Series User Manual

Page 81

Advertising
background image

Troubleshooting | 78

Display Message

LED

System

Detected

Cause

Corrective Action(s)


Foaming Cylinder
Warning / Fault


Red

4 Humidifier short cycling

4 Observe operation to

ensure humidifier can
normally run long
enough to perform a
drain. If not turn on the
Short Cycle feature on
page 56.

Low Conductivity
Warning


Low water
conductivity

1 Drain valve leaking

1 Clean drain valve or

replace (see
maintenance chapter)

2 Back pressure causing

some fill water to go
down drain

2a Check for restrictions

and proper condensate
removal in steam line.

2b If water is going down

drain during fill cycle
then install fill cup
extension kit.

3 Wrong Cylinder Installed 3 Install cylinder of same

model number as was
previously installed

4 Newly installed cylinder

not reaching demand
for extended time due
to Low water
conductivity

4a Add 1/4 teaspoon of

salt to fill cup.

4b Adjust drain factor to

0.7 in User Defined
Settings (see operation
chapter)

4c Turn on the Low

Conductivity feature on
page 56.

Max Level Warning

Water level at
top of cylinder or
foaming

1 Humidifier has filled to

top of cylinder without
reaching demand

1 None, for information

only, it is normal for a
new cylinder to reach
max level before water
in cylinder is
concentrated and for an
old cylinder to reach
max level near the end
of cylinder life.

1b If the cylinder is new,

add ¼ teaspoon of salt
to fill cup to assist
cylinder in
concentrating.

1c Supply water

conductivity too low (DI
or RO). Change to
potable water supply
with conductivity above
150 µS/cm.

Advertising