Remote fault option wiring – Nortec NH-EL Series User Manual

Page 36

Advertising
background image

33 | Installation

Steam

Unit ON

Error

Service

NO

COM

NO

COM

NC

NO

COM

NC

NO

COM

Remote Fault Option Wiring

The NH-EL remote fault option includes 4 relays that can provide remote status indication. The
relays are mounted to a remote fault board which is located as shown in Figure 31: Remote
Fault Wiring. T
he PCB with the relays includes markings which indicate the function of each
terminal on the board. The relays indicate the following status:
1 Unit On – The normally open relay is closed when the humidifier has power and the On/Off

switch is set to on.

2 Steam – The normally open relay is closed when the control board detects that the cylinder

is drawing current and steam is being produced.

3 Service – The relay can be wired to open (NC) or close (NO) when a warning is displayed on

the humidifier display and the yellow service LED is illuminated.

4 Error – The relay can be wired to open (NC) or close (NO) when a fault is detected by the

humidifier controls.





















Figure 31: Remote Fault Wiring