Nortec NH-EL Series User Manual

Page 82

Advertising
background image

79 | Troubleshooting

Display Message

LED

System

Detected

Cause

Corrective Action(s)

2 Water foaming

2 Check if water level is at

top of cylinder. If water
is not at top there may
be foam in the cylinder.
Consider the Foam
Mode
feature on page
55.

No Current Fault

Red

Water level at
top of cylinder
with no current

1 Current transformer

loose on driver board

1 Open disconnect,

ensure current
transformer spade
connectors are secure.
Squeeze with pliers if
loose.

2 Primary wire not looped

through current
transformer.

2 Open disconnect, rewire

primary wire through
current transformer.

3 High water sensor plug

is on an electrode pin.

3 Install high water sensor

plug on cylinder pin with
shroud around it.

Remote Disabled
Warning

Network
shutdown
message

1 Network signal received

by humidifier to shut
down.

1 Normal operation for

humidifier on network
control. Contact network
administrator to enable
humidifier.

RH High Warning

RH higher than
high RH setpoint

1 Setpoint higher than RH

alarm setting

1 If the humidifier is still

operating then check
and adjust setpoints.

RH Low Warning

RH Lower than
low RH setpoint

1 Humidifier not running

1 Check why humidifier is

not running and put it
into operation.

2 Setpoint lower than RH

low alarm setting

2 Check and adjust

setpoints.

Safety Loop Open

Grn
Blink

Security loop
open (terminal 1
and 2)

1 On/Off device

connected to security
loop is open

1a Normal operation, no

action required

1b Wrong setpoint, A/P

not sensing air
movement

2 Loose wire

2 Check wiring to all

On/Off devices
connected to terminals
1 and 2.

SIM Card Fault

Red

Controller cannot
detect a valid
SIM card

1 Improper SIM card

installation or missing

1 Check that SIM card is

installed and socket
closed.

2 Incorrect SIM card

2 Check that the SIM card

serial number matches
the humidifier’s.