69 | Maintenance and Servicing

NH-EL Maintenance Checklist

Model #: _________________

Serial #: _________________

Tag: ________

Cylinder #:


Cylinder / System Check

Warning Cylinder Spent

Fault Cylinder Spent

(If software displays Warning Cylinder Spent then cylinder must be replaced)

Yellow LED On with Max Level Warning.

(If Yellow LED is On with Max Level Warning and cylinder is not new, cylinder may have to be replaced soon.)

Other warnings or Faults shown in display?

No

Yes

(See Troubleshooting Chapter for actions to address warnings and faults if present

)

Replace Cylinder

Cylinder drained.

Disconnect open, On/Off switch to Off, water shut off valve closed, door removed.

Cylinder removed

Drain valve removed / cleaned / new O-Ring

Drain valve installed / ground wire attached.

New Cylinder Installed and hose clamps tight (12 in-lbs for 7/8” steam hose and 16 in-lbs

for 1 ¾” steam hose).

New cylinder model #

(Should be same as removed cylinder)

Cylinder plug colors match cylinder dots.

Cylinder plugs snug and in good condition.

High Water Sensor plug snug and in good condition.

Electrical wiring not loose and in good condition.

Steam hoses and steam lines in good condition / No kinks in hose.

No Signs of water leaking around humidifier, steam line, condensate returns.

Door replaced, water shut off valve opened, On/Off switch to On, Disconnect Closed.

“Reset Cylinder” in Software, (press cylinder status, Password 0335).


Inspected by:

Date of inspection: _______/_______/______

Company: