Troubleshooting | 76

Table 11: Troubleshooting Warnings and Faults

Display Message

LED

System

Detected

Cause

Corrective Action(s)

BMS
BACnet
Nortec Online
Staged
Modulation
Warning/Fault

Red

No Modbus/
BACnet / Nortec
Online / Multi
Mode signal

1 Loose connection

1 Check connections and

polarity of wires.

2 Incorrect

Modbus/BACnet/IP
address or
configuration.

2 Check that address of

humidifier matches that
of network.

3 Humidifier configured

but not connected to
network

3 Configure controls

correctly in “Control
Setting” level of
software (see Operation
Chapter).

4 Improper wire used

4 Use 120 Ohm

impedance shielded
twisted pair cable for
Modbus, Cat 5 for
BACnet IP/ IP.

5 Noise preventing

humidifier from
detecting signal.

5 Eliminate source of

noise causing
interference.

Control Signal
Warning / Fault

No signal from
RH control
sensor






No signal from
RH Limit sensor

1 Sensor not powered

1 Use multimeter to

check that sensor is
powered.

2 Sensor not wired

correctly

2 Check wiring is secure

and wired correctly per
instructions in
installation chapter.

3 Defective sensor

3 Check if sensor output

is corresponding to RH.
If not replace the
sensor.

Red

4 RH less than 5%

4 RH less than 5% are

interpreted as a broken
sensor. Contact
NORTEC Representative
for recommendation.

Red

5 Humidifier control

configuration incorrect

5 Check that the

humidifier control
configuration matches
the installed sensor
output.

Current Off Fault Red

Current detected
with no demand

1 Contactor seized closed 1 Open Disconnect, check

if contactor is closed

2 Driver Board out of

Calibration

2 If display indicates

output with contactor
open, then replace the
driver board.