Troubleshooting | 80

Display Message

LED

System

Detected

Cause

Corrective Action(s)

Staged
Modulation
Warning

Red

Slave unit not
communicating
with Master Unit.

1 Master unit not

configured correctly

1 Check configuration of

master as outlined in
Multi Mode
Configuration

2 Slave unit not

configured correctly

2 Check configuration of

slave as outlined in
Multi Mode
Configuration

3 Wiring to master unit

disconnected

3 Check that wire

connected to J10 of
Master and Slave and
that polarity is not
reversed

4 Incorrect wire type used 4 Use 18-24 AWG multi-

strand, twisted pair,
shielded cable

Unstable Control
Warning

Demand
swinging from
low to high
rapidly

1 Improper Proportional

and Integral settings in
control

1 Adjust proportional and

integral settings to
reduce swings in
demand signal.

2 Control humidistat

installed too close to
diffuser or doorway to
un-humidified space

2 Install humidistat so

that it senses air
representative of space
being humidified.

3 Defective control

3 Replace defective

control