Installation | 12

Table 5: Clearances for Blower Packs on Low Speed*

Humidifier

Capacity

lbs/hr (kg/hr)

Minimum

No. of

Blower

Packs

Min. Frontal

Clearance

Inches (cm)

Min. Overhead

Clearance

Inches (cm)

Min. Left side

Clearance

Inches (cm)

Min. Right side

Clearance

Inches (cm)

30 (13.6)

1

132 (336)

12(31)

12 (31)

12 (31)

100 (45.4)

1

Not

recommended

Not

recommended

Not

recommended

Not

recommended

Table 6: Clearances for Blower Packs on High Speed*

Humidifier

Capacity

lbs/hr (kg/hr)

Minimum

No. of

Blower

Packs

Min. Frontal

Clearance

Inches (cm)

Min. Overhead

Clearance

Inches (cm)

Min. Left side

Clearance

Inches (cm)

Min. Right side

Clearance

Inches (cm)

30 (13.6)

1

120 (305)

12(31)

12 (31)

12 (31)

100 (45.4)

1

248 (630)

36 (91)

30 (76)

30 (76)

*NOTES:

Nominal Conditions 72˚F (22.2˚C), 43% RH.
Low speed not recommended for 100 lbs/hr humidifier. Consult factory for recommendations.
Blower Pack should not be installed near cold surfaces or where dew point may be reached.
Higher humidity or lower room temperature may result in longer absorption distances.