Modbus digital control, Wiring, Modbus communication requirements – Nortec NH-EL Series User Manual

Page 38

Advertising
background image

35 | Installation

Modbus Digital Control

The NH-EL humidifier comes standard with a Modbus communication interface. The Modbus
interface can be configured to control the humidifiers output or can be used to monitor its
operation. See Nortec document 2560599 – Using Modbus with Nortec Humidifiers for a listing
of Modbus parameters that are available with the NH-EL.

Wiring

Table 8 provides information on Modbus wiring requirements. The NH-EL uses a three pole
terminal, the Integrated Controller PCB, to provide Modbus communications. Connections can
be made directly to this terminal.

Table 8: Modbus Wiring Requirements

BMS

Protocol

Signal Type

Recommended

Cable

Max. Recommended Distance

from Nortec Module to BMS

Modbus

EIA-485,

2-wire

18-24 AWG

Shielded, Twisted

Pair, 120 Ω*

Should not exceed 2200 ft

* Connect humidifiers in daisy chain to the Modbus RTU. Ground shield at one end only (BMS or humidifier)

Modbus Communication Requirements

Table 9: Modbus Communication Parameters lists the requirements for Modbus communication
with the NH-EL and the range of adjustable parameters. Adjustable parameters are set using
the LCD touchscreen of the NH-EL in the Factory Menu Level which is not accessible to users. If
the parameters must be changed from default, refer to the Nortec document 2560599 – Using
Modbus with Nortec Humidifiers.

Table 9: Modbus Communication Parameters

Item

Default

Adjustment Range

Signal Type*

EIA-485

-

Transmission Mode*

RTU

-

Baud Rate

9600

9600, 19200,

38400, 115200

Data Bits*

8

-

Stop Bits*

1

-

Parity

Even

Odd, Even, None

Address

1

1-247

Timeout

300 s

0-300 s

* Parameters not adjustable

Advertising