11 | Installation

6 in.

(15 cm)

Recommended

Side

Clearance

36 in. (91.5 cm)

Min. Front Clearance

24 in.(61 cm)

Min Height

Mount Humidifier

Level

5-95%

(See Table for

Blowerpack

clearances)

(See Table for

Blowerpack

clearances)

(See Table for

Blowerpack
clearances)

If Blowerpack is used,

mount so that the steam

outlet is at least

96 in. (244 cm)

above ground level.

Location

Mount on a suitable wall or vertical surface. Do not sit the unit on the floor to allow

clearances required for plumbing and electrical connections.

Clearance dimensions shown are for reference only and are the minimum required for

maintenance of the humidifier. Consult local and national codes before final location and
installation. NORTEC does not accept responsibility for installation code violations.

Install only in areas with ambient temperature 41-104 °F (5 – 40 °C) relative humidity 5 -

95% (non condensing).

When possible install the humidifier below the steam distributor. Take care to provide proper

steam line routing and proper condensate traps.

DO NOT locate the humidifier any further than absolutely necessary from the steam

distributor location. Net output will be reduced as a result of heat loss through the steam
line.

When possible, mount the NH-EL humidifier at a height convenient for servicing.



Figure 5: Mounting Location / Clearance


Note: Do not mount on hot surfaces, where freezing can occur, vibrating surface, or

floor.