Section 7: Confi guring Analog Outputs

GPC-XP Controller Technical Guide

32

Outdoor Air Enable, Controlling Schedule, Enabling Relay

Outdoor Air Enable

If this option is used, the Outdoor Air Temperature must be between
these setpoints for this Analog Output to function. See Figure 61
below
.

Figure 61: Outdoor Air Enable Setpoints

Controlling Schedule

No matter what Control Method or Control Source has been selected,
each analog output can be confi gured to follow a schedule. See Fig-
ure 62 below
. Actual Schedules are set in the Schedules Window.
See instructions on page 35 for setting Schedules.

Enabling Relay

An Enabling Relay can also be selected. The operation of this Analog
Output will only occur once the Enabling Relay (based on its logic)
has energized. See Figure 63 below.

Figure 63: Enabling Relay

Enabling Binary Input

An Enabling Binary Input can also be selected (Figure 64 below).
The operation of this Analog Output will only occur once the selected
Binary Input is Active.

For example, if the Binary Input selected is confi gured as “N/O Con-
tact (Closes for Active),” then this Analog Output is enabled when
24 VAC is applied and the N/O Binary Input contact closes (Active).

If the Binary Input selected is confi gured as “N/C (Opens for Ac-
tive),” then this Analog Output will be enabled when 24 VAC is
removed and the N/C Binary Input contact opens (Active).

Figure 64: Enabling Relay Binary Input

Output Voltage Limits

This output normally operates with a range of 0-10 VDC. If you need
it to operate with a different Min and/or Max voltage, those voltages
can be entered in the Output Voltage Limits Box (Figure 65 below).

Figure 65: Output Voltage Limits

Figure 62: Controlling Schedule