Communication settings, Gpc-xp controller technical guide, Before applying power – Orion System GPC-XP Controller User Manual

Page 7: Connect on board commlink, Stand alone operation, Network operation, Figure 3: gpc-xp controller address switch setting, On-board commlink setting, Ao ut 1 -2, Gpc-xp controller

Advertising
background image

GPC-XP Controller Technical Guide

Section 1: GPC-XP Wiring & Setup

7

Communication Settings

Before Applying Power

In order to have a trouble free start-up, it is important to follow a
few simple procedures. Before applying power for the fi rst time, it
is very important to correctly address the controller and run through
a few simple checks.

Communication Settings

Stand Alone Operation

The GPC-XP has an on-board CommLink that is used during Stand-
Alone Operation. When confi gured for Stand-Alone operation, a
computer running Prism 2 software can be connected directly to the
USB port located at the bottom of the GPC-XP for programming
and monitoring. In order to operate in Stand-Alone Mode, two
things need to be set. First, both CommLink Jumpers found on the
upper left hand side of the board need to be set to ON. See Figure

3

below

for details. Second, the Baud Rate determined by setting

ADDRESS Dipswitches 7 and 8 needs to be set to OFF/ON. See
Figure 4, page 8 for details.

NOTE: If using the Internal CommLink, you must set up

the USB drivers. See Appendix B, page 52.

Network Operation

The GPC-XP can be confi gured for connection to a networked system
that has an external CommLink. In this case, the on-board CommLink
would not be used. For this confi guration, two things need to be set.
First, both CommLink Jumpers found on the upper left found on the
upper left hand side of the board need to be set to OFF. See Figure
3

below

for details. Second, the Baud Rate determined by setting

ADDRESS Dipswitches 7 and 8 needs to be set to OFF/OFF if us-
ing a CommLink IV and to OFF/ON if using a CommLink 5. See
Figure 4, page 8 for details.

Figure 3: GPC-XP Controller Address Switch Setting

GPC-XP Controller

CO

M
F

R

O

M
G

ND

CUT

TO

IS

O

L

A

T

E

WATTMASTER CONTROLS

YS102432 REV 3

LOOP COMM

GND

+24V

+5V

OUTPUTS

ADDRESS

ADD

1

2
4
8

16

32

POWER

EBUS

STATUS2

STATUS1

OUTPUTS

ANALOG

SERIAL #

OUTPUTS

RELAY

SH

R+

T-

BIN8

BIN7

BIN6

BIN5

BIN4

BIN3

BIN2

BIN1

BINARY
INPUTS

INPUTS

ANALOG

0-5

v

0-10

v

4-

2

0

m

A

AO

UT

1

-2

C14

R109

TB8

U19

U17

TB7

TB6

TB4

TB3

TB2

TB1

SW1

R97

R74

R6
1

R59

R5
5

R51

R47

R4
3

R4
1

R3
8

R21

R16

R14

D13

D12

D10

D9

D8

D7

D6

C46

C36

C21

RLY1

RLY2

RLY3

RLY4

COMMON

MADE IN USA

RLY1

RLY2

RLY3

RLY4

COMMON

AOUT1

AOUT2

AOUT3

AOUT4

GND

GND

1002

1002

.1uF

.1uF

AO

UT

3

-4

GND

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.01uF

L

OOP

BAU

D

1

2

AI7

AI8

AI6

AI5

AI4

AI1

AI2

AI3

GND

GND

GND

GND

AI8

AI7

AI6

AI5

AI4

AI3

AI2

AI1

TH
E

R

M

VDC

300

300

300

300

300

300

300

300

COM

COM

COM

COM

D11

CONNEC

ON BOA
COMMLI

ON-BOARD COMMLINK SETTING

Jumper 2

ON

Jumper 1

OFF

ON

OFF

Use On-Board CommLink

Setting

Use External CommLink

CONNECT

ON BOARD
COMMLINK

Both Jumpers ON

CONNECT

ON BOARD
COMMLINK

Both Jumpers OFF

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

RELAY 2

RELAY 6

RELAY 1

RELAY 5

RLY 1 =

VDC

OUTPUTS

AI1 =

+ 24 VDC

+ 5 VDC

GND

BI1 =

AO1 =

AI2 =

BI2 =

AO2 =

AI3 =

BI3 =

AO3 =

AI4 =

BI4 =

AO4 =

AI5 =

BI5 =

AI6 =

BI6 =

AI7 =

BI7 =

AI8 =

BI8 =

RLY 2 =

RLY 5 =

RLY 3 =

RLY 6 =

RLY 4 =

RLY 7 =

RLY 8 =

RELAY 3

RELAY 7

RELAY 4

RELAY 8

COMMON

COMMON

USB

PORT

E-BUS

PORT

NOTES:
1.) ANALOG INPUT JUMPER SETTINGS MUST BE
SET FOR YOUR SPECIFIC INPUT DEVICE
REQUIREMENT.

2.) IT IS RECOMMENDED THAT YOU WRITE THE
DESCRIPTION OF THE INPUT, AND/OR
OUTPUTS YOU ARE CONNECTING TO THE
CONTROLLER IN THE BOXES PROVIDED ABOVE
USING A PERMANENT MARKER (SHARPIE) FOR
FUTURE REFERENCE.

®

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.wattmaster.com

AI1

AI2

AI3

AI4

AI5

AI6

AI7

AI8

THE

R

M

4-20

mA

0-

10

V

0-

5V

ANALOG

INPUT

JUMPERS

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SCHEDULE OVERRIDE

0

2

OE338-23-GPC-XP

GPC-XP CONTROLLER

WattMaster Label

#LB102095

Rev.: 1C

+2

4

VA

C

GND

Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.

Caution:
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.