Addressing and baud rate settings, Zone, Figure 4: gpc-xp controller address switch setting – Orion System GPC-XP Controller User Manual

Page 8: Ao ut 1 -2, Baud rate selection

Advertising
background image

Zone

Zone

Section 1: GPC-XP Wiring & Setup

GPC-XP Controller Technical Guide

8

Controller Addressing and Baud Rate

The GPC-XP Controller is equipped with address switches. When
using Prism 2 to program and confi gure the GPC-XP Controller, you
would enter this address to communicate with the controller. When
the system is to be connected to other HVAC unit controllers on a
communication loop, each controller’s address switch must be set
with a unique address between 1 and 59.

Figure 4: GPC-XP Controller Address Switch Setting

GPC-XP Controller

16

32
Baud 0
Baud 1

8

4

2

1

Address Switch Shown Is

Set For Address 1

Address Switch Shown Is

Set For Address 13

Controller
Address Switch

Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.

Caution:
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.

Address 1 @ 9600 Baud

ADD

ADD

ADD

The Address For Each Controller

Must Be Unique To The Other Controllers

On The Local Loop And Be Between 1 and 59

CO

M
F

R

O

M
G

ND

CUT

TO

IS

O

L

A

T

E

WATTMASTER CONTROLS

YS102432 REV 3

LOOP COMM

GND

+24V

+5V

OUTPUTS

ADDRESS

ADD

1

2
4
8

16

32

POWER

EBUS

STATUS2

STATUS1

OUTPUTS

ANALOG

SERIAL #

OUTPUTS

RELAY

SH

R+

T-

BIN8

BIN7

BIN6

BIN5

BIN4

BIN3

BIN2

BIN1

BINARY
INPUTS

INPUTS

ANALOG

0-5

v

0-10

v

4-

2

0

m

A

AO

UT

1

-2

C14

R109

TB8

U19

U17

TB7

TB6

TB4

TB3

TB2

TB1

SW1

R97

R74

R6
1

R59

R5
5

R51

R47

R4
3

R4
1

R3
8

R21

R16

R14

D13

D12

D10

D9

D8

D7

D6

C46

C36

C21

RLY1

RLY2

RLY3

RLY4

COMMON

MADE IN USA

RLY1

RLY2

RLY3

RLY4

COMMON

AOUT1

AOUT2

AOUT3

AOUT4

GND

GND

1002

1002

.1uF

.1uF

AO

UT

3

-4

GND

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

1002

.1uF

.01uF

LO
O

P

BAU

D

1

2

AI7

AI8

AI6

AI5

AI4

AI1

AI2

AI3

GND

GND

GND

GND

AI8

AI7

AI6

AI5

AI4

AI3

AI2

AI1

TH
E

R

M

VDC

300

300

300

300

300

300

300

300

COM

COM

COM

COM

D11

CONNEC

ON BOA
COMMLI

BAUD RATE SELECTION

Switch 7 Switch 8

9600

Baud

57600

OFF

OFF

ON

OFF

16

32
Baud 0
Baud 1

8

4

2

1

Address 5 @ 57,600 Baud

ADD

CommLink IV

Communication Setting

CommLink 5 & Stand Alone

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

RELAY 2

RELAY 6

RELAY 1

RELAY 5

RLY 1 =

VDC

OUTPUTS

AI1 =

+ 24 VDC

+ 5 VDC

GND

BI1 =

AO1 =

AI2 =

BI2 =

AO2 =

AI3 =

BI3 =

AO3 =

AI4 =

BI4 =

AO4 =

AI5 =

BI5 =

AI6 =

BI6 =

AI7 =

BI7 =

AI8 =

BI8 =

RLY 2 =

RLY 5 =

RLY 3 =

RLY 6 =

RLY 4 =

RLY 7 =

RLY 8 =

RELAY 3

RELAY 7

RELAY 4

RELAY 8

COMMON

COMMON

USB

PORT

E-BUS

PORT

NOTES:
1.) ANALOG INPUT JUMPER SETTINGS MUST BE
SET FOR YOUR SPECIFIC INPUT DEVICE
REQUIREMENT.

2.) IT IS RECOMMENDED THAT YOU WRITE THE
DESCRIPTION OF THE INPUT, AND/OR
OUTPUTS YOU ARE CONNECTING TO THE
CONTROLLER IN THE BOXES PROVIDED ABOVE
USING A PERMANENT MARKER (SHARPIE) FOR
FUTURE REFERENCE.

®

24 VAC POWER ONLY

WARNING! POLARITY MUST BE OBSERVED

OR THE CONTROLLER WILL BE DAMAGED

www.wattmaster.com

AI1

AI2

AI3

AI4

AI5

AI6

AI7

AI8

THE

R

M

4-20

mA

0-

10

V

0-

5V

ANALOG

INPUT

JUMPERS

LED BLINK CODES

LED NAME

STATUS1

STATUS2

NORMAL OPERATION

0

1

SCHEDULE OVERRIDE

0

2

OE338-23-GPC-XP

GPC-XP CONTROLLER

WattMaster Label

#LB102095

Rev.: 1C

+2

4

VA

C

GND

Address switches 7 and 8 are used for the baud rate selection. See
Figure 4

below

for address switch and baud rate setting information.

Addressing and Baud Rate Settings

Advertising