Implicit addressing, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual

Page 12: Pt-link ii interface 12, Explicit and implicit addressing

Advertising
background image

PT-Link II LON

®

Technical Guide

PT-Link II Interface

12

Implicit Addressing

Explicit and Implicit Addressing

Clients can address the PT-Link using explicit or implicit addressing.
Clients using explicit addressing obtain their data transfer parameters
directly from the PT-Link II LON confi guration fi le (confi g.csv). Implicit
addressing is used when a Network Management Tool such as LonMaker®
is used to connect a PT-Link II LON to other LonWorks nodes—the
PT-Link II LON is assigned its data transfer (binding) parameters by
the Network Management Tool.

NOTE: The PT-Link II LON is confi gured from the factory to

use implicit addressing.

Implicit Addressing

— Network Manager assigns addresses for

communication and ensures (via address tables in the devices) that
communication connections are known.

Explicit Addressing

— Device knows the address of the point in

the remote device and communicates directly without the assistance of
the Network Manager.

Implicit Addressing Commissioning Using

LonMaker

1.) Ensure that the correct fi rmware and latest confi guration is

loaded on the PT-Link II LON.

NOTE: Each change in the PT-Link II LON requires re-commis-

sioning of the PT-Link II LON in LonMaker.

2.) Ensure that the PT-Link II LON and the LonMaker machine

are on the same network.

3.) Open the existing Network in LonMaker or create a new
Network.

4.) Click on <Create New Network> and follow the network

wizard, making the following selections:

Network Interface:

Choose Network Attached

Management Mode:

Choose Onnet unless you are

working

offl ine

Registered Plug-ins required

: None

5.) Once Visio is open with the Network showing, drag a new

device onto the drawing from the toolbox.

6.) Follow the Device Network, making the following
selections:

Enter Device Name

: Choose commission device

Specify Device Template

: Choose upload from device

Specify Device Channel

: Choose Auto Detect

Specify Device Properties

: Leave as is (Ping is optional)

Identify Device

: Choose service pin

Device Application Image

: Leave unchecked

Initial State

: Leave as is

7.) Press the service pin on the PT-Link II LON when asked to

do so, and the PT-Link II LON will be commissioned.

8.) Drag a new function block onto the drawing from the

toolbox. Give the function block a name and ensure that it

is allocated to the PT-Link II LON device.

9.) Once the function block is on the drawing, you can drag

input and output variables onto the function block. When

you do this, LonMaker will show you the variables

avail able for binding. Click on the variables you require

(or use the select “all” option), and they will be

commissioned onto the function block.

10.) You are now ready to connect these variables to other

devices by dragging connections from the toolbox and

connecting the variables.