Appendix f - sa controller lon parameters, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual

Page 52: Pt-link ii interface 52, Sa controller pt-link ii lon, Property identifi er

Advertising
background image

PT-Link II LON

®

Technical Guide

PT-Link II Interface

52

Appendix F - SA Controller LON Parameters

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Proof of

Water Flow

Alarm

PoWFAlm

Binary
Output

Alarm that indicates no

Proof of Water Flow.

Entering Air
Temperature

Alarm

EaTpAlm

Binary
Output

Alarm that indicates

failure in the Entering Air

Temperature Sensor.

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Space

Temperature

Sensor Lost

SpcTpAlm

Binary
Output

Alarm that indicates a failure in

the space temperature sensor.

On Board

Relay 1

OnRly1

Binary
Output

Current status of relay 1.

On Board

Relay 2

OnRly2

Binary
Output

Current status of relay 2.

On Board

Relay 3

OnRly3

Binary
Output

Current status of relay 3.

On Board

Relay 4

OnRly4

Binary
Output

Current status of relay 4.

On Board

Relay 5

OnRly5

Binary
Output

Current status of relay 5.

Expansion

Relay 1

ExRly1

Binary
Output

Current status of relay 6.

Expansion

Relay 2

ExRly2

Binary
Output

Current status of relay 7.

Expansion

Relay 3

ExRly3

Binary
Output

Current status of relay 8.

Expansion

Relay 4

ExRly4

Binary
Output

Current status of relay 9.

Expansion

Relay 5

ExRly5

Binary
Output

Current status of relay 10.

Expansion

Relay 6

ExRly6

Binary
Output

Current status of relay 11.

Expansion

Relay 7

ExRly7

Binary
Output

Current status of relay 12.

Expansion

Relay 8

ExRly8

Binary
Output

Current status of relay 13.

Expansion

Relay 9

ExRly9

Binary
Output

Current status of relay 14.

Expansion

Relay 10

ExRly10

Binary
Output

Current status of relay 15.

Expansion

Relay 11

ExRly11

Binary
Output

Current status of relay 16.

Expansion

Relay 12

ExRly12

Binary
Output

Current status of relay 17.

Expansion

Relay 13

ExRly13

Binary
Output

Current status of relay 18.

Expansion

Relay 14

ExRly14

Binary
Output

Current status of relay 19.

Expansion

Relay 15

ExRly15

Binary
Output

Current status of relay 20.

Expansion

Relay 16

ExRly16

Binary
Output

Current status of relay 21.

Emergency

Shutdown

Alarm

EmerAlm

Binary
Output

Alarm that indicates

Emergency Shutdown.

Drain Pan

Overfl ow

DrnAlm

Binary
Output

Alarm that indicates overfl ow of

the drain pan.

SA Controller PT-Link II LON

®

Property Identifi er:

The PT-Link II LON

®

Link amends the following property identity to

the LON

®

property identifi er.

LONPropertyIdentifi er :

SAUnitMode ::= ENUMERATED {

Unoccupied

(0),

RemoteContactOccupied (1),
NormalScheduleOccupied

(2),

PushButtonOrZoneOverride

(3),

HolidayModeActive

(4),

UnoccupiedZoneDemand

(5),

RemoteScheduleOverride (6),
CurrentOutputForceMode

(7),

SATHighOrLowCutOff

(8),

CO2OverrideInProgress

(9),

PurgeModeActive

(10)

}

SAControlStatusBits ::= ENUMERATED {

Off

(0),

Vent

(1),

Cool

(2),

Heat

(3),

Dehum

(4),

Dehum

Cool

(5),

Dehum

Heat

(6),

Warm

Up

Mode

(7)

}

Advertising