Page 51: Technical guide 51

Advertising
background image

PT-Link II Interface

PT-Link II LON

®

Technical Guide

51

Appendix F - SA Controller LON Parameters

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Unoccupied

Heating

Offset

UnHtOst

Analog

Input

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Heating Setpoint

out by a user

adjustable amount.

If you do not want
Heating to operate

during the Unoc-

cupied Mode, use

the default setting

of 30°F for these

setpoints.

0

30

Static

Pressure
Setpoint

DuctPrSt

Analog

Input

This is the target

duct pressure to be

maintained by the

VFD blower signal.

0.01

3

Preheater

Setpoint

PreHtSp

Analog

Input

Low Outside Air

Ambient

Protection Setpoint

0

100

Entering

Air Offset

Setpoint

EaTpOst

Analog

Input

If the Entering

Air Temperature

Sensor is reading

incorrectly, you

can use this option

to enter an offset

temperature to

adjust the Sensor’s

Temperature.

Entering

Water

Offset

Setpoint

EwTpOst

Analog

Input

If the Entering

Water Temperature

Sensor is reading

incorrectly, you

can use this option

to enter an offset

temperature to

adjust the

Sensor’s

Temperature.

Bad Supply

Air Sensor

SaTpAlm

Binary
Output

Alarm that

indicates a failure

in the supply air

sensor.

Cooling

Enabled

ClEnbl

Binary

Output

Status that indicates
mechanical cooling

is enabled.

Economizer

Enabled

EcoEnbl

Binary
Output

Status that indicates

the economizer is

enabled.

Fan Start Up

Delay

FanDly

Binary

Output

Status that indicates

the fan is com-

manded to run, but

it is in the start up

delay mode.

SNVTs for the SA Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Fan

Proving

Alarm

PofAlm

Binary
Output

Alarm that indicates a failure in

the fl ow of the VFD blower.

Heating

Enabled

HtEnbl

Binary
Output

Status that indicates that

mechanical heating is enabled.

High

Supply Air

Temperature

Alarm

HiSaAlm

Binary
Output

The Supply Air has risen above

the Hi SAT Cutoff Setpoint.

Heating stages begin to

deactivate and the fan

continues to run.

Low Supply

Air

Temperature

Alarm

LoSaAlm

Binary
Output

The Supply Air has fallen below

the Hi SAT Cutoff Setpoint and

cooling stages will begin to

deactivate. If the unit is in

Economizer, Vent, or Heating

Mode the Supply Fan

will shut off.

MODGAS II

Connected

MdHt2Ins

Binary
Output

Status that indicates

the MODGAS II controller

is connected.

REHEAT II

Connected

Rt2Ins

Binary
Output

Status that indicates

the MHGRV

controllers is connected

to the system.

Mechanical

Cooling

Alarm

MchClAlm

Binary
Output

Compressor Relays are enabled
but the Supply Air Temperature

has not fallen 5°F w/in a user-

adjustable time period. This does

not indicate compressors are

active and will not

shut the unit down.

Mechanical

Heating

Alarm

MchHtAlm

Binary
Output

Heating Mode has been initiated

but the Supply Air Temperature

has not risen 5°F w/in a

user-adjustable time period.

This does not indicate heat

stages are active and will not

shut the unit down.

Dirty Filter

Detected

DrtFlAlm

Binary
Output

Alarm that indicates

the fi lters are dirty.

Control

Temperature
Cool Failure

CtrlTpCF

Binary
Output

This alarm is activated if the
control temperature does not

get within 5°F to the occupied

cooling setpoint in an hour in the

cooling mode. This alarm is not

used in 100% outside air units or

supply air control.

Control

Temperature

Heat Failure

CtrlTpHF

Binary
Output

This alarm is activated if the
control temperature does not

get within 5°F to the occupied

heating setpoint in an hour in the

heating mode. This alarm is not

used in 100% outside air units or

supply air control.