Appendix g - vcm lon parameters, Pt-link ii interface, Pt-link ii lon – Orion System PT-Link II LON User Manual

Page 55: Technical guide 55, Snvts for the vcm controller

Advertising
background image

PT-Link II Interface

PT-Link II LON

®

Technical Guide

55

Appendix G - VCM LON Parameters

SNVTs for the VCM Controller

Binary Output SNVTs are SNVT_lev_disc

All other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Supply

Air Sensor

Offset

SaTpOst

Analog

Input

If the Supply Air

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Unoccupied

Cooling

Offset

UnClOst

Analog

Input

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Cooling Setpoint

out by a user

adjustable amount.

If you do not want
Cooling to operate

during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

Unoccupied

Heating

Offset

UnHtOst

Analog

Input

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Heating Setpoint

out by a user

adjustable amount.

If you do not want
Heating to operate

during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

Dewpoint

Setpoint

DptSt

Analog

Input

If the outdoor

dewpoint rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

35

80

SNVTs for the VCM Controller

Binary Output SNVTs are SNVT_lev_disc

All other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Indoor

Humidity

Setpoint

InRhSt

Analog

Input

If the indoor

humidity rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

0

100

Warm Up

Setpoint

WmupSt

Analog

Input

In a VAV

application, upon

entering the

occupied mode, the

Warm-up Demand

will be activated

if the return air

temperature falls

one degree below

this setpoint.

50

90

Wet Bulb

Setpoint

WtblSt

Analog

Input

The economizer is

enabled if the out-

door temperature

or wetbulb falls

below this setpoint.

0

80

Bad Supply

Air Sensor

SaTpAlm

Binary
Output

Alarm that

indicates a failure

in the supply air

sensor.

CO

2

Sensor

Installed

CO2Cfg

Binary
Output

Status that

indicates the CO

2

function has been

confi gured.

Cooling

Demand

ClDmnd

Binary
Output

Status that

indicates a demand

for cooling.

Cooling
Enabled

ClEnbl

Binary
Output

Status that indicates
mechanical cooling

is enabled.

Economizer

Enabled

EcoEnbl

Binary
Output

Status that indicates

the economizer is

enabled.

Fan Start

Up Delay

FanDly

Binary
Output

Status that indicates

the fan is

commanded to run,

but it is in the start

up delay mode.

Fan

Proving

Alarm

PofAlm

Binary
Output

Alarm that

indicates a failure

in the fl ow of the

VFD blower.

Heating

Demand

HtDmnd

Binary
Output

Status that indicates

a demand for

heating.

Advertising