Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Low Control

Mode Tem-

perature

LoCtrlMd

Binary
Output

Occurs when

the Control-

ling Sensor

Temperature

falls below the

Heating Mode

Enable Setpoint

minus the Con-

trol Mode Low

Alarm Offset.

Applies only to

Space or Return

Air Tempera-

ture controlled

units.

Cooling Low
Reset Source

ClLoRt

Analog

Input

If doing Supply

Air Setpoint

Reset, this is

the Low Reset

Source value

in Cooling that

will correspond

to the Supply

Air Cool High

Reset Setpoint.

1

150

Cooling High

Reset Source

ClHiRt

Analog

Input

If doing Supply

Air Setpoint

Reset, this is

the High Reset

Source value

in Cooling that

will correspond

to the Supply

Air Cooling

Setpoint (Low

Reset).

1

150

Condenser

Control Signal

CdCtrSg1

Analog

Output

Condenser Fan

Signal 1 Status.

Controlling

Sensor High

Alarm Offset

CTpHiAlm

Analog

Input

If the tempera-

ture of the con-

trolling sensor

rises above the

Occupied Cool-

ing Setpoint

by this value,

a High Control

Temp Alarm

will occur.

Only applies if

confi gured for

Space or Return

Air Temp

Control, or as

Single Zone

VAV.

0

50

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Controlling

Sensor Low

Alarm Offset

CTpLoAlm

Analog

Input

If the tempera-

ture of the con-

trolling sensor

falls below the

Occupied Heat-

ing Setpoint

by this value,

a Low Control

Temp Alarm

will occur.

Only applies if

confi gured for

Space or Return

Air Temp

Control, or as

Single Zone

VAV.

0

50

Control Status

CtrlSts

Analog

Output

Current

operational

status.

See Control

Status Bits on

page 38.

Control

Temperature

CtrlTp

Analog

Output

Current value

of the control

temperature

sensor.

Cooling
Enabled

ClEnbl

Analog

Output

Status that

indicates

mechanical

cooling is

enabled.

Mechani-

cal Cooling

Lockout

MchClLkt

Analog

Input

The VCB-X

will Lockout

Mechanical

Cooling when

the Outdoor Air

Temperature
is below this

Setpoint.

-30

100

Mechani-

cal Cooling

Alarm

MchClAlm

Binary
Output

Compressor

Relays are

enabled but

the Supply Air

Temperature has

not fallen 5°F

within a user-

adjustable time

period. This

does not apply

for Modulating

Cooling.

Cooling

Setpoint

Mirror

ClSt

Analog

Output

Occupied

Cooling Mode

Enable

Setpoint.

Revised 7/7/14