Appendix c - vcb-x lon parameters, Pt-link ii interface, Pt-link ii lon – Orion System PT-Link II LON User Manual

Page 31: Technical guide 31

Advertising
background image

PT-Link II Interface

PT-Link II LON

®

Technical Guide

31

Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Exhaust Fan

CFM

EtCFM

Analog

Output

Current

Exhaust

Airfl ow

Measurement

Exhaust Fan

Speed

EtFnSpd

Analog

Output

Current

value of the

VFD relief

fan signal.

Missing

Exhaust CFM

Sensor

ExtCfmSr

Binary
Output

Indicates that

the Exhaust

CFM Sensor is

not detected.

Missing EM1

Expansion

Module

MisEM1

Binary
Output

Indicates that

the EM1 Ex-

pansion Module

is not

communicating

with the VCB-

X Controller.

Fan

Starting Delay

FanDly

Analog

Output

Indicates the

current fan

status related

to request to

run, fan starting

delay or POF

failure.

0=No Request

1=Fan

Running

2=Fan Start

Delay

3=POF Failure

Force HVAC

Mode

FrcHvacM

Analog

Input

Overrides

normal control-

ler operation in

order to force

the unit into

this desired

mode. Con-

fi guring for

“Auto” will

restore normal

unit control of

the mode of

operation.

0=Auto

1=Vent

2=Cool
3=Heat

4=Vent

Dehum.

5=Cool

Dehum.

6=Heat

Dehum.

Leaving H2O

Offset

LvH2OOst

Analog

Input

If the Leaving

Water Tem-

perature Sensor

is reading

incorrectly, use

this to enter an
offset to adjust

the Sensor’s

Temperature.

-100

100

Water Proof of

Flow Failure

H2OProf

Binary
Output

Indicates no

Proof of Water

Flow.

Head

Pressure

HeadPr

Analog

Output

Current value

of the Head

Pressure

Reading.

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Head

Pressure
Setpoint

HeadPrSt

Analog

Output

Current Head

Pressure

Setpoint.

Head

Pressure

Setpoint in

Cooling Mode

ClHdPrSt

Analog

Input

This is the

Head Pressure

Setpoint the

unit will control

to in the

Cooling Mode.

240

PSI

420

PSI

Head

Pressure
Setpoint

in Reheat

Mode

HtHdPrSt

Analog

Input

This is the

Head Pressure

Setpoint the

unit will control

to in the De-

humidifi cation

Reheat Mode.

240

PSI

420

PSI

High Head

Pressure

HiHedPr

Binary
Output

Indicates the

Head Pressure

is too high.

Heating

Enabled

HtEnbl

Analog

Output

Status that

indicates that

mechani-

cal heating

is enabled to

operate.

SAT Heating

Low Reset

Source

HtLoRt

Analog

Input

If doing Supply

Air Setpoint

Reset, this is

the Low Reset

Source value

in Heating that

will correspond

to the

Supply Air

Heating High

Reset Setpoint.

1

150

SAT Heating

High Reset

Source

HtHiRt

Analog

Input

If doing Supply

Air Setpoint

Reset, this is

the High Reset

Source value

in Cooling that

will correspond

to the Supply

Air Cooling

Setpoint (Low

Reset).

1

150

Heating

Setpoint

Mirror

HtSt

Analog

Output

Occupied

Heating Mode

Enable

Setpoint.

Revised 7/7/14