Appendix e - vcm-x lon parameters, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual

Page 44: Pt-link ii interface 44

Advertising
background image

PT-Link II LON

®

Technical Guide

PT-Link II Interface

44

Appendix E - VCM-X LON Parameters

SNVTs for the VCM-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Modulating

Heat

Position

MdHtPos

Analog

Output

Current position of

the modulating

heating signal (hot

water or SCR heat).

Unit Mode

UnitMode

Analog

Output

See page 48.

Return Air
CO

2

Level

CO2Level

Analog

Output

Current value of the

CO

2

sensor.

Bypass

Damper
Position

ByPas-

Dmp

Analog

Output

Current position of

the bypass damper

signal.

Return

Damper
Position

RaDmp

Analog

Output

Current position of

the return damper

signal.

Coil

Temperature

CoilTp

Analog

Output

Current coil

temperature reading

added on version

1.09.

Outdoor Air

CFM

OaCFM

Analog

Output

Current Outdoor

Airfl ow

Measurement

Exhaust

CFM

EtCFM

Analog

Output4

Current Exhaust

Airfl ow

Measurement

Supply Air

CFM

SaCFM

Analog

Output

Current Supply

Airfl ow

Measurement

Current

Calculated

OA CFM

setpoint

OACfm-

StM

Analog

Output

Current calculated

Outdoor Air CFM

based on CO

2

level.

Dewpoint

Setpoint

DptSt

Analog

Input

If the outdoor

dewpoint rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

35

80

Occupied/

Mode

Enable

Cooling

Setpoint

OcpClSt

Analog

Input

If the control tem-

perature rises one
degree above this

setpoint, the control

will activate the

cooling demand.

If the control

temperature is the

Supply Air Sensor,

then the cooling

demand is always

active.

0

99

SNVTs for the VCM-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Occupied/

Mode

Enable

Heating

Setpoint

OcpHtSt

Analog

Input

If the control

temperature drops

one degree below

this setpoint,

the control will

activate the heating

demand. If the

control

temperature

is the Supply

Air Sensor, then

there is no heating

demand.

99

Outdoor

Air Sensor

Offset

OaTpOst

Analog

Input

If the Outdoor

Temperature Sensor

is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Return

Air Sensor

Offset

RaTpOst

Analog

Input

If the Return Tem-

perature Sensor is

reading incorrectly,

you can use this

option to enter an

offset temperature

to adjust the Sen-

sor’s Temperature.

-100

100

Schedule

Force

SchdFrc

Analog

Input

0 = Auto/

Unoccupied Mode

1 = Forced On

2 = Forced Off

0

2

Space

Sensor

Offset

SpcTpOst

Analog

Input

If the Space

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

SAT

Cooling

Setpoint

SaClSt

Analog

Input

Supply Air Setpoint

in Cooling Mode.

40

80

SAT

Heating

Setpoint

SaHtSt

Analog

Input

Supply Air setpoint

in Heating Mode.

40

200

Supply

Air Sensor

Offset

SaTpOst

Analog

Input

If the Supply Air

Temperature Sensor

is reading incor-

rectly, you can use

this option to enter

an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Revised 11/16/10