Appendix c - vcb-x lon parameters, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual

Page 32: Pt-link ii interface 32

Advertising
background image

PT-Link II LON

®

Technical Guide

PT-Link II Interface

32

Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Heat Staging

Window

HtStgWdw

Analog

Input

In the Heating

Mode, if the

Supply Air

Temperature

rises above the

Active Supply

Air Heating

Setpoint plus

the Heating

Stage Off

Window value,

a Heating stage

will be deacti-

vated after its

Minimum Run

Time.

1

50

Mechani-

cal Heating

Lockout

MchHtLkt

Analog

Input

The VCB-X

will Lockout

Mechanical

Heating when

the Outdoor Air

Temperature
is above this

Setpoint.

-30

150

Mechanical

Heating Alarm

MchHtAlm

Binary
Output

Heating Mode

has been

initiated but

the Supply Air

Temperature has

not risen 5°F

within a user-

adjustable time

period. This

does not This

does not apply

for Modulating

Heating.

Heat Pump

Compressor

Heating

Outdoor
Lockout

HpLkt

Analog

Input

Compressor

Heating will

be locked

out when the

Outdoor Air

Temperature
is below this

Setpoint.

-30

100

Heat Pump

Defrost

Interval

HpDfrInt

Analog

Input

The Heat Pump

Defrost Interval

is the length of

time that must

be met between
Defrost Modes.

10

Min

120

Min

Heat Wheel

Defrost

Setpoint

Dfrst

Analog

Input

The unit will

go into Heat

Wheel Defrost

Mode when the

Outdoor Air

is below this

setpoint.

0

50

Revised 7/7/14

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Indoor

Humidity

InRh

Analog

Output

Current value

of the indoor

humidity

sensor.

Indoor

Humidity

Setpoint

InRhSt

Analog

Input

If Coil Temp

Reset is being

used this is

also the lowest

Space RH value

that

corresponds

to the Hi Coil

Temp Setpoint.

0

100

High Indoor

Humidity

Reset Limit

HiInRh

Analog

Input

During Coil

Temp Reset,

this is the high-

est Space RH

value that

orresponds to

the Low Coil

Temp Setpoint.

0

100

Indoor

Humidity

Setpoint

Mirror

InRhStM

Analog

Output

Mirror of the
InRhSt “read

only.”

Leaving Water

Temperature

LvWtrTp

Analog

Output

Leaving Water

Temperature

Value

Low

Ambient

Relay

Setpoint

LWAmbnt

Analog

Input

Temperature at
which the Low

Ambient Relay

will activate in

the Occupied

or Unoccupied

Mode.

-30

70

Mode Select

Deadband

MdSelDb

Analog

Input

This Setpoint

is added to

and subtracted

from the HVAC

Mode Setpoints

to determine

when the unit

enters and

leaves a mode

of operation.

1

10

Modulating

Cooling
Position

MdClPos

Analog

Output

Current

position of the

modulating

cooling signal

(Chilled water

or digital

compressor).

Modulating

Gas Valve

Position

MdGs

VPos

Analog

Output

Current posi-

tion of

MODGAS

modulating gas

valve control.

Advertising