Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Outdoor
Wetbulb

OaWtbl

Analog

Output

Current cal-

culated value

of the outdoor

wetbulb

temperature.

Preheat

Relay

Setpoint

PreHtAmb

Analog

Input

If the Supply

Fan is ener-

gized this is the

temperature

at which the

Preheat Relay

will activate.

Operates only

in the Occupied

Mode.

-30

70

Proof of Flow

Alarm

PofAlm

Binary
Output

Indicates no

Proof of Water

Flow.

Reheat

Enabled

RehtEnbl

Binary
Output

Modulating

Hotgas Reheat

Enabled.

Reheat Valve

Position

RtVlvPos

Analog

Output

Current

position of

MHGRV

modulating

hot gas reheat

valve.

Missing

Reheat

Module

MisMH-

GRV

Binary
Output

Indicates that

the MHGRV

Module is not

communicating

with the VCB-

X Controller.

Return Air

CFM

RaCFM

Analog

Output

Current Return

Airfl ow

Measurement.

Missing

Return Air

CFM Sensor

RaCfmSr

Binary
Output

Indicates

that the Return

Air CFM

Sensor is not

detected.

Return Air

Damper
Position

RaDmp

Analog

Output

Current Return

Air Damper

position.

Return Air

Humidity

RaRH

Analog

Output

Current value

of the Return

Air Humidity

Sensor.

Return Air

Temperature

RaTp

Analog

Output

Current value

of the return

temperature

sensor.

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Return Air

Temperature

Sensor Offset

RaTpOst

Analog

Input

If the Return

Temperature

Sensor is

reading

incorrectly, use

this to enter an
offset to adjust

the Sensor’s

Temperature.

-100

100

Bad Return

Air Sensor

RaTpAlm

Binary
Output

Indicates a

failure of the

Return Air

Sensor.

Return Bypass

Damper
Position

RetBydmp

Analog

Output

Current Return

Bypass Damper

position.

Schedule

Force

SchdFrc

Analog

Input

0 = Auto (uses

controller’s

schedule)

1 = Forced

Occupied

2 = Forced

Unoccupied

0

2

Current Slide
Adjust Offset

SldAdOfs

Analog

Output

Current Slide
Adjust Offset

value.

Smoke Alarm

/ Emergency

Shutdown

SmokeAlm

Binary
Output

Indicates the

Smoke sen-

sor has been

activated. This

will shut down

the unit.

Space

Temperature

SpcTp

Analog

Output

Current value

of the space
temperature

sensor.

Space

Temperature

Offset

SpcTpOst

Analog

Input

If the Space

Temperature

Sensor is

reading

incorrectly, use

this option to

enter an offset

to adjust the

Sensor’s

Temperature.

-100

100

Space

Temperature

Sensor

Lost

SpcTpAlm

Binary
Output

Indicates

a failure of the

Space Tempera-

ture Sensor.

Static

Pressure

StaticPr

Analog

Output

Current Static

Pressure.

Static

Pressure
Setpoint

StatPrSt

Analog

Input

Current Static

Pressure

Setpoint.

.10

3.0

Revised 7/7/14