SNVTs for the VCM-X WSHP (Tulsa) & RNE

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Low Water

Temperature 1

Alarm

LWT1Alm

Binary
Output

Alarm that

indicates water

temperature is

below the Leav-

ing Water Safety

Setpoint (Heating

only) for System

A.

Low Water

Temperature 2

Alarm

LWT2Alm

Binary
Output

Alarm that

indicates water

temperature is

below the Leav-

ing Water Safety

Setpoint (Heating

only) for System

B

Proof of Water 1

Flow Alarm

POWF1Alm

Binary
Output

Alarm that

indicates no Proof

of Water Flow for

System A (A1/

A2)

Proof of Water 2

Flow Alarm

POWF2Alm

Binary
Output

Alarm that

indicates no Proof

of Water Flow for

System B (B1/

B2)

Module

Communica-

tions Alarm

ComMAlm

Binary
Output

Alarm that

indicates that one

or more Modules

are not

communicating

with the VCM-X

WSHP Controller.

Bad Return Air

Sensor

RaTpAlm

Binary
Output

Alarm that indi-

cates

a failure in the

Return Air Sen-

sor.

Title 24

Economizer

Alarms

AlmGrp5

Analog

Output

Alarms for the 24

Title Economizer

Title 24

Economizer

Feedback

T24EcFb

Analog

Output

Current position

of feedback from

Economizer

actuator.

Appendix D - VCM-X WSHP Tulsa & RNE LON Parameters

SNVTs for the VCM-X WSHP (Tulsa) & RNE

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Title 24

Sensor Alarm

T24TpAlm

Binary
Output

Outside Air

or Supply Air

Temperature Sen-

sor is shorted or

missing.

Title 24 Not

Economizing

When It Should

T24NEWS

Binary
Output

Economizer is

enabled but not

following the

desired Econo-

mizer position

commanded.

Title 24 Econo-
mizing When It

Should Not

T24EWISN

Binary
Output

Economizer is

not enabled but

the feedback

signal indicates
a position more

open than the

minimum.

Title 24 Damper

Failure

T24DpAlm

Binary
Output

Economizer is

enabled but not

within 10% of

desired posi-

tion within 150

seconds.

Title 24 Excess

Outdoor Air

T24ExsOA

Binary
Output

Economizer

feedback is lost or
Economizer is not

following com-

manded position.