Appendix G - VCM LON Parameters

SNVTs for the VCM Controller

Binary Output SNVTs are SNVT_lev_disc

All other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Application

Software

Version

AppVer

Analog

Output

Current version of the

software in the unit.

Alarm

Status

AlrmSts

Analog

Output

See

page

58.

Unit Mode

UnitMode

Analog

Output

See

page

58.

Control

Status

CtrlSts

Analog

Output

Current operational

status.

Control

Temperature

CtrlTp

Analog

Output

Current value of the con-

trol temperature sensor.

Occupied/

Mode

Enable

Cooling

Setpoint

Mirror

ClSt

Analog

Output

Occupied/ Mode

Enable Cooling Setpoint

Mirror.

Duct Static

Pressure

DuctPr

Analog

Output

Current value of the duct

static pressure sensor.

Economizer

Position

EcoPos

Analog

Output

Current position of the

economizer damper.

External

Relays 1-2

ExRlys12

Analog

Output

See

page

58.

External

Relays 3-4

ExRlys34

Analog

Output

See

page

58.

Indoor

Humidity

InRh

Analog

Output

Current value of the

indoor humidity sensor.

Occupied/

Mode

Enable

Heating

Setpoint

Mirror

HtSt

Analog

Output

Occupied/ Mode

Enable Heating Setpoint

Mirror.

On Board

Relay

OnRlys

Analog

Output

See

page

58.

Outdoor Air

Humidity

OaRh

Analog

Output

Current value of the out-

door humidity sensor.

Outdoor Air

Temperature

OaTp

Analog

Output

Current value of the out-
door temperature sensor.

Outdoor Air

Wetbulb

OaWtbl

Analog

Output

Current calculated value

of the outdoor wetbulb

temperature.

Relief

Pressure

RfPr

Analog

Output

Current value of the

building pressure sensor.

Return Air
CO

2

Level

CO2Level

Analog

Output

Current value of the CO

2

sensor.

Return Air

Temperature

RaTp

Analog

Output

Current value of the re-

turn temperature sensor.

SNVTs for the VCM Controller

Binary Output SNVTs are SNVT_lev_disc

All other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Space

Temperature

SpcTp

Analog

Output

Current value of

the space tempera-

ture sensor.

Supply Air

Temperature

SaTp

Analog

Output

Current value of

the supply air

temperature sensor.

Temperature

Demand

TpDmnd

Analog

Output

Based on the com-

parison between

the current Control

Temperature and

the Heating or

Cooling Setpoint

Temperatures.

Does not work for
supply air control.

VFD

Blower Fan

VfdBwPos

Analog

Output

Current position

of the VFD blower

fan signal.

VFD Relief

Fan

VfdExPos

Analog

Output

Current position of

the VFD relief

fan signal.

Modulating

Gas Valve

Position

MdHt2Pos

Analog

Output

Current position

of MODGAS II

modulating gas

valve control.

Reheat

Value

Position

Rt2Pos

Analog

Output

Current position of

MHGRV

modulating hot

gas reheat valve

control.

Alarm

Group 1

AlrmGrp1

Analog

Output

See

page

58.

Alarm

Group 2

AlrmGrp2

Analog

Output

See

page

58.

Alarm

Group 3

AlrmGrp3

Analog

Output

See

page

58.

Dewpoint

Setpoint

Mirror

DptStM

Analog

Output

Mirror of the DPtSt

“read only.”

Indoor RH

Setpoint

Mirror

InRhStM

Analog

Output

Mirror of the

InRhSt “read only.”

Modulating

Cool

Position

MdClPos

Analog

Output

Current position of

the modulating

cooling signal

(Chilled water or

digital compressor).

Modulating

Heat

Position

MdHtPos

Analog

Output

Current position of

the modulating

heating signal

(hot water or SCR

heat).

Bypass

Damper
Position

ByPasDmp

Analog

Output

Current position of

the bypass damper

signal.