Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

High Coil

Temperature

Setpoint

Limit

HiClTpSt

Analog

Input

This is the

highest that the

Coil Tem-

perature will be

reset to during
Space Humid-

ity Reset of the

Coil Suction
Temperature

Setpoint. If no

coil tem-

perature reset

is required, this

value should be

set the same as

the Low Coil

Temperature

Setpoint.

35

70

Low Coil

Temperature

Setpoint

Limit

LoClTpSt

Analog

Input

This is the low-
est that the Coil

Temperature

will be reset to

during Space

Humidity Reset
of the Coil Suc-

tion Tempera-

ture Setpoint.

If no coil tem-

perature reset

is required, this

value should be

set the same as

the High Coil

Temperature

Setpoint.

35

70

Compressor

Discharge

Temperature

DschgTp

Analog

Output

Current value

of the Compres-

sor Discharge

Temperature

Sensor.

Bad Compres-

sor Discharge

Sensor

DschgAlm

Binary
Output

Failure of

the Digital

Compressor

Discharge

Temperature

Sensor.

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Control Mode

CtrlMod

Analog

Output

1=Constant

Volume

2=Supply Air
Cooling Only

3=Outdoor

Temp Control

4=Single Zone

VAV

5=Supply Air

Tempering

6=Space Temp

Control w/

High OA

Content

Unoccupied

Control Tem-

perature Cool-

ing Failure

CtrlTpCF

Binary
Output

Activated if the
control temper-

ature does not

get within 5°F

to the occupied

cooling setpoint

in an hour in

the cooling
mode. This

alarm is not

used in 100%

outside air units

or supply air

control.

Control Tem-

perature Heat-

ing Failure

CtrlTpHF

Binary
Output

Activated if the
control temper-

ature does not

get within 5°F

to the occupied

heating setpoint

in an hour in

the heating

mode. This

alarm is not

used in 100%

outside air units

or supply air

control.

High Control

Mode Tem-

perature

HiCtrlMd

Binary
Output

Occurs when

the Control-

ling Sensor

Temperature

rises above the

Cooling Mode

Enable Setpoint

plus the Control

Mode High

Alarm Offset.

Applies only to

Space or Return

Air Tempera-

ture controlled

units.

Revised 7/7/14