Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Static

Pressure
Setpoint

Deadband

DuctPrDb

Analog

Input

Value above

and below the

Duct Static

Pressure Set-

point where no

control change

occurs.

Suction Pres-

sure

SucPr

Analog

Output

Current Suction

Pressure value.

High Suction

Pressure

Alarm

HiSucPr

Binary
Output

Indicates

Suction Pres-

sure is above

the High Suc-

tion Pressure

Cooling (Heat-

ing) Setpoint.

Low Suction

Pressure

Alarm

LoSucPr

Binary
Output

Indicates

Suction Pres-

sure is below

the Low Suc-

tion Pressure

Cooling (Heat-

ing) Setpoint.

Supply Air

CFM

SaCFM

Analog

Output

Current Supply

Airfl ow

Measurement.

High Supply

Air Tempera-

ture Alarm

HiSaAlm

Binary
Output

The Supply Air
has risen above

the High SAT

Cutoff Setpoint.

Heating stages

begin to deacti-

vate and the fan

continues to run.

Low Supply

Air Tempera-

ture Alarm

LoSaAlm

Binary
Output

The Supply Air

has fallen below

the Low SAT

Cutoff Setpoint

and cooling

stages will begin

to deactivate.

If the unit is in

Economizer,

Vent, or Heat-

ing Mode the

Supply Fan will

shut off.

Supply Air

Cooling

Setpoint

SaClSt

Analog

Input

Supply Air

Cooling Set-

point. If Supply

Air Reset is

confi gured, this
is the Low SAT

Cooling Reset

Value.

30

80

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Supply Air

Heating

Setpoint

SaHtSt

Analog

Input

Supply Air

Heating Set-

point. If Supply

Air Reset is

confi gured, this
is the Low SAT

Heating Reset

Value.

40

240

Supply Air

Cool High

Reset

SaClRt

Analog

Input

If Supply

Air Reset is

confi gured, this

is the High SAT

Cooling Reset

Value.

0

100

Supply Air

Heat High

Reset

SaHtRt

Analog

Input

If Supply

Air Reset is

confi gured, this

is the High SAT

Heating Reset

Value.

0

250

Supply Air

Temperature

SaTp

Analog

Output

Current value

of the

supply air

temperature

sensor.

Bad Supply

Air Tempera-

ture Sensor

SaTpAlm

Binary
Output

Indicates a

failure of the

Supply Air

Temperature

Sensor.

Low Supply

Air Temp

Cutoff

LoSaCf

Analog

Input

Cooling will

be disabled if

the Supply Air

Temperature

falls below

this value. See

sequence for

more details.

0

100

High Supply

Air Temp

Cutoff

HiSaCf

Analog

Input

Heating will

be disabled if

the Supply Air

Temperature

rises above

this value. See

sequence for

more details.

0

250

Supply Air

Temperature

Offset

SaTpOst

Analog

Input

If the Supply

Air

Temperature

Sensor is read-

ing incorrectly,

you can use this

option to enter

an offset

temperature to

adjust the

Sensor’s

Temperature.

-100

100

Revised 7/7/14