Appendix c - vcb-x lon parameters, Pt-link ii lon, Technical guide – Orion System PT-Link II LON User Manual

Page 30: Pt-link ii interface 30

Advertising
background image

PT-Link II LON

®

Technical Guide

PT-Link II Interface

30

Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Cool Staging

Window

ClStgWdw

Analog

Input

In Cooling

Mode, if the

Supply Air

Temperature

drops below the

Active Supply

Air Cooling

Setpoint minus

this Staging

Window, a

Cooling Stage
will be deacti-

vated after its

Minimum Run

Time.

1

30

Adaptive

Defrost

Interval

Adjustment

AptDfr

Analog

Input

Adjustment to

the Heat Pump

Defrost Interval

depending on

whether the

Defrost Mode

lasts 10 minutes

or less than 10

minutes.

0 Min

30

Min

Dewpoint

Setpoint

RhDewpSt

Analog

Input

On a MUA unit,

if the outdoor

dewpoint rises

above this

setpoint, the

unit will

activate Dehu-

midifi cation.

35

80

Digital Com-

pressor Cutoff

DigCmpCf

Binary
Output

Occurs if

the digital

compressor

discharge tem-

perature rises

above 268°F
or the sensor

is shorted. The

compressor is

disabled.

Digital

Compressor

Lockout

DigCmpLk

Binary
Output

Occurs if fi ve

Digital Com-

pressor Cutoffs

occur within

four hours. The

compressor will

be locked out.

Dirty Filter

Alarm

DrtFlAlm

Binary
Output

Alarm that

indicates the

fi lters are dirty.

Economizer

Enabled

EcoEnbl

Analog

Output

Status that

indicates

the economizer

is enabled.

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Economizer

Enable

Setpoint

EcoEnbSt

Analog

Input

The economizer

is enabled if the

outdoor dry-

bulb, dewpoint,

or wetbulb

temperature

falls below this

setpoint.

-30

80

Economizer

Position

EcoPos

Analog

Output

Current

position of the

economizer

damper.

Max Econo-

mizer in Heat

Mode

MaxEcoHt

Analog

Input

Max position

the Economizer

Damper can

open in the

Heating Mode.

Takes priority

over Max Posi-

tion in High

CO

2

.

0%

100%

Max

Economizer

in High CO2

Mode

MaxEcoCO

Analog

Input

The maximum

value the

Economizer

Minimum

Position can

be reset up to

during CO

2

override.

0%

100%

Minimum

Economizer

Position

MinEcoSt

Analog

Input

Minimum

position of the

economizer in

the occupied

mode.

0

100

Force

Economizer

FrcEcono

Analog

Input

Overrides all

other Outdoor

Air Damper

position com-

mands so as to

maintain this

fi xed position.

Confi guring

for “Auto” will

restore normal

unit control of

the Outdoor

Air Damper/

Economizer

operation.

0%

100%

Auto=65535

Emergency

Heat Enabled

EmHtEnbl

Binary
Output

Shows the

Emergency

Heat is enabled

based on the

Compres-

sor Heating

Lockout.

Advertising